225 CMR 16.05
Eligibility Criteria for APS Alternative Generation Units
(1) Eligibility Criteria. A Generation Unit may qualify as an APS Alternative Generation Unit
subject to the limitations in 225 CMR 16.05.
(a) Technologies. The Generation Unit shall use one or more of the technologies listed in
225 CMR 16.05(1)(a)1. through 6.
1. Gasification. This technology is no longer eligible because it was eliminated
pursuant to M.G.L. c. 25A, § 11F½.
2. Combined Heat and Power. A Generation Unit that is operated to produce Combined
Heat and Power may qualify as an APS Alternative Generation Unit, subject to the
limitations in 225 CMR 16.05(1)(a)2.
a. CHP Metering and Reporting Requirements. A CHP Unit shall provide for the
metering of electrical energy generated, Useful Thermal Energy produced, and fuel
consumed; for calculating the net quantity of MWh for which Alternative Energy
Attributes are qualified, and for reporting to the NEPOOL GIS of that net qualified
MWh quantity in a manner prescribed in 225 CMR 16.05(1)(c), for each quarter of
the Compliance Year. Monitoring, reporting, and calculating of electrical energy and
Useful Thermal Energy produced in that quarter shall be expressed in MWh, and the
total of all fuel and any other energy consumed in that quarter is calculated using the
energy content of the fuel based on higher heating value.
b. Determination of APS Alternative Energy Attributes. The Generation Unit shall
be provided APS Alternative Energy Attributes as specified in 225 CMR
16.05(1)(a)2.b.
i. A CHP Unit which produced neither electrical nor Useful Thermal Energy
before January 1, 2008, shall be provided APS Alternative Energy Attributes
equal to the result, if positive, of the following calculation: take the sum of:
(i) the electrical energy generated divided by the overall efficiency of
electrical energy delivered to the end-use from the electrical grid (which
efficiency is equal for this purpose to 0.33); and
(ii) the Useful Thermal Energy divided by the overall efficiency of thermal
energy delivered to the end-use from a standalone heating unit (which
efficiency is equal for this purpose to 0.80); and subtract from this sum the
total of all fuel and any other energy consumed by the CHP Unit in that
quarter expressed in MWh and calculated using the energy content of the fuel
based on its higher heating value.
ii. A CHP Unit which produced either or both electrical and Useful Thermal
Energy before January 1, 2008, and added either or both Incremental Useful
Thermal Energy or Incremental Electrical Energy after such date, shall be
provided APS Alternative Energy Attributes equal to the result, if positive, of the
following calculation: take the sum of:
(i) the Incremental Electrical Energy generated divided by the overall
efficiency of electrical energy delivered to the end-use from the electrical grid
(which efficiency is equal for this purpose to 0.33); and
(ii) the Incremental Useful Thermal Energy divided by the overall
efficiency of thermal energy delivered to the end-use from a standalone
heating unit (which efficiency is equal for this purpose to 0.80); and subtract
from this sum the total of all Incremental Fuel and any other incremental
energy consumed by the CHP Unit in that quarter expressed in MWh and
calculated using the energy content of the fuel based on its higher heating
value.
c. Energy Deliverability Requirement. The CHP Unit shall deliver Useful Thermal
Energy to an end-use load located in the Commonwealth of Massachusetts.
3. Flywheel Storage Unit. A Flywheel Storage Unit that stores and discharges electrical
energy may qualify as an APS Alternative Generation Unit, subject to the limitations in
225 CMR 16.05(1)(a)3.
a. The Flywheel Storage Unit must participate in the ISO-NE regulation market.
b. The portion of the electrical energy output of a Flywheel Storage Unit that may
qualify for APS Alternative Generation shall be calculated each quarter of the
Compliance Year as 65% of the electrical energy discharged from the Flywheel
Storage Unit during the quarter.
c. The electrical energy output, the calculation made to derive the net quantity of
MWh for which Alternative Energy Attributes are qualified and that net MWh
quantity shall be reported to the NEPOOL GIS as specified in 225 CMR 16.05(1)(c).
4. Paper-derived Fuel. This technology is no longer eligible because it was eliminated
pursuant to M.G.L. c. 25A, § 11F½.
5. Efficient Steam Technology. (Reserved)
6. APS Renewable Thermal Generation Unit. A Generation Unit that uses one or more
of the technologies provided in 225 CMR 16.05(1)(a)6.a. and generates Useful Thermal
Energy may qualify as an APS Alternative Generation Unit, subject to the limitations in
225 CMR 16.05(1)(a)6.a. and the provisions in 225 CMR 16.05(4).
a. Eligible APS Renewable Thermal Generation Unit technologies and standards:
i. Air-source Heat Pump. An air-source heat pump Generation Unit uses
compression and evaporation to transfer thermal energy from the ambient outdoor
environment to a thermal load as Useful Thermal Energy. The Generation Unit
must be designed to operate effectively in cold climates, such that the air-source
heat pump provides meaningful net annual reductions in conventional energy use.
Air-source heat pumps are provided APS Alternative Energy Attributes only
when operating in a heating mode; that is, when transferring thermal energy from
the ambient outdoor environment to a thermal load. An applicant must
demonstrate to the satisfaction of the Department that the air-source heat pump
is the primary source of heating for the residential Generation Unit, building, or
process it serves, and meets the design criteria, as provided in the Department's
Guideline on Metering and Calculating the Useful Thermal Output of Eligible
Renewable Thermal Generation Units.
ii. Ground Source Heat Pump. A ground source heat pump Generation Unit
uses compression and evaporation to transfer thermal energy from the ambient
underground or water environment to a thermal load as Useful Thermal Energy.
The Generation Unit must receive all applicable permits, approvals, and
registrations from the MassDEP. An applicant must demonstrate to the
satisfaction of the Department that it meets the design criteria, as provided in the
Department's Guideline on Metering and Calculating the Useful Thermal Output
of Eligible Renewable Thermal Generation Units. Ground or water-source heat
pumps are provided APS Alternative Energy Attributes only when operating in
a heating mode; that is, when transferring thermal energy from the ambient
underground or water environment to a thermal load.
iii. Deep Geothermal Heat Exchange. A deep geothermal heat exchange
Generation Unit uses hot geological formations deep below the ground surface
to produce heat through direct heat exchange. The Generation Unit must receive
all applicable permits, approvals, and registrations from the MassDEP, and must
demonstrate to the Department it can operate at or above minimum performance
requirements as provided in the Department's Guideline on Metering and
Calculating the Useful Thermal Output of Eligible Renewable Thermal
Generation Units.
iv. Solar Thermal. A solar thermal Generation Unit uses collectors, to transfer
solar irradiation energy to a working fluid, as well as a pump or fan to actively
circulate the air, water, or other working fluid through the collectors. Solar
thermal collectors must have a performance certification issued by the Solar
Rating and Certification Corporation, International Association of Plumbing and
Mechanical Officials, or other performance certification approved by the
Department. Unglazed flat plate collectors for pool heating are not eligible to
qualify as an APS Renewable Thermal Generation Unit.
v. Woody Biomass. A woody biomass Generation Unit must use automatically
fed boilers or furnaces, and must utilize either Eligible Biomass Woody Fuel, or
bio-oil refined through pyrolysis or biogas derived from Eligible Biomass Woody
Fuel. Woody biomass Generation Units must meet the provisions regarding
efficiency, system performance, use of thermal energy storage, particulate matter
and carbon monoxide emissions, fuel supply sustainability, fuel quality, and
greenhouse gas emissions in 225 CMR 16.06(4)(g). and the Department's
Guideline on Biomass, Biogas and Biofuels for Eligible Renewable Thermal
Generation Units, as well as receive all applicable permits from the MassDEP.
vi. Biogas. A biogas Generation Unit uses Eligible Biogas Fuel derived from
either an Anaerobic Digester, as that term is defined in 310 CMR
7.70(10)(b): Definitions, or a landfill that has received all applicable permits
from the MassDEP or comparable environmental agency responsible for
regulating such facilities. Eligible Biogas Fuel must be conveyed directly from
its source to the biogas Generation Unit in a dedicated pipeline. Biogas
Generation Units may co-fire with other fuels subject to the provisions in 225
CMR 16.05(2), and must meet quality and performance criteria provided in the
Department's Guideline on Biomass, Biogas and Biofuels for Eligible Renewable
Thermal Generation Units.
vii. Liquid Biofuels. A liquid biofuel Generation Unit must use Eligible Liquid
Biofuels. Liquid biofuel Generation Units may co-fire with other fuels subject
to the provisions in 225 CMR 16.05(2), but shall contain at least 10% by volume
Eligible Liquid Biofuel. The liquid biofuels Generation Unit must meet quality
and performance criteria provided in the Department's Guideline on Biomass,
Biogas and Biofuels for Eligible Renewable Thermal Generation Units, must
receive all applicable permits from the MassDEP, and is subject to the provisions
in 225 CMR 16.05(4)(f).
viii. Compost Heat Exchange System. A Generation Unit that uses a facility to
recover or exchange heat from the aerobic biodegradation of organic matter
during the production of compost.
b. Determination of APS Alternative Generation Attributes. Each Generation Unit
listed in 225 CMR 16.05(1)(a)6. shall earn APS Alternative Energy Attributes as
specified in 225 CMR 16.05(1)(a)6.b., 225 CMR 16.05(4), and in the Department's
Guideline on Metering and Calculating the Useful Thermal Output of Eligible
Renewable Thermal Generation Units, as follows:
i. An APS Renewable Thermal Generation Unit shall earn APS Alternative
Energy Attributes for each MWh of net Useful Thermal Energy generated on a
quarterly basis.
ii. Earned APS Alternative Energy Attributes shall be for the generation of
Useful Thermal Energy, net of any fossil fuel energy and electrical energy input
to the APS Renewable Thermal Generation Unit necessary for its operation,
however, the Department may exclude small energy uses including, but not
limited to, fans, pumps, meters, controls, and data collection. The Department
shall prescribe the calculations for netting energy input from the Useful Thermal
Energy in the Department's Guideline on Metering and Calculating the Useful
Thermal Output of Eligible Renewable Thermal Generation Units.
iii. Notwithstanding 225 CMR 16.05(1)(a)6.b.i., APS Alternative Energy
Attributes for an APS Renewable Thermal Generation Unit that meets the criteria
of a small Generation Unit, as defined in the Department's Guideline on Metering
and Calculating the Useful Thermal Output of Eligible Renewable Thermal
Generation Units, may be pre-minted in one calendar quarter in a quantity equal
to the APS Alternative Generation Attributes that the small Generation Unit is
deemed to generate over its qualification period; as prescribed in 225 CMR
16.05(4)(c).
c. Energy Deliverability Requirement. An APS Renewable Thermal Generation
Unit shall deliver Useful Thermal Energy to an end-use load located in the
Commonwealth of Massachusetts.
d. Combination of Funding. If a Generation Unit receives funding in an amount
exceeding 80% of the Generation Unit's total construction and installation costs from
a grant or incentive program administered by the Department or any other state
agency prior to December 29, 2017, the Generation Unit shall not be eligible to
qualify in the APS.
7. Fuel Cell. A Fuel Cell Generation Unit that produces electricity and/or Useful
Thermal Energy may qualify as an APS Alternative Generation Unit, subject to the
limitations in 225 CMR 16.05(1)(a)7.
a. Source of Hydrogen. A Fuel Cell Generation Unit that uses hydrogen generated
through the use of propane shall be required to certify that the propane was
manufactured using only natural gas.
b. Overall Efficiency. To qualify as an APS Alternative Generation Unit, a Fuel
Cell Generation Unit shall be more efficient than the current average for emitting
locational marginal units as based on the heat rates for these units shown in the most
recent ISO-NE Electric Generator Air Emissions Report available in the same year
in which a Fuel Cell Generation Unit submits an SQA. A Fuel Cell Generation Unit
that generates both electricity and Useful Thermal Energy must have an overall
efficiency of at least 55%. The overall efficiency of a Fuel Cell Generation Unit shall
be calculated as the sum of the MWh of electricity generated, excluding any
electricity utilized for parasitic load, plus the MWh of Useful Thermal Energy,
divided by the total higher heating MWh value of fuel consumed by the Fuel Cell
Generation Unit. Supporting operating data, confirming that the Fuel Cell
Generation Unit continues to meet the Overall Efficiency requirement in 225 CMR
16.06(1)(a)7.b., must be submitted to the Department on an annual basis in order for
the Fuel Cell Generation Unit to maintain its Statement of Qualification.
c. Attribute Multiplier. A Fuel Cell Generation Unit shall earn 1½ APS Alternative
Energy Attributes for each MWh of electricity and/or 3,412,000 British thermal units
of net Useful Thermal Energy generated. A Fuel Cell Generation Unit shall retain
the multiplier, provided at its time of qualification, as long as it continues to meet all
other applicable eligibility criteria in 225 CMR 16.05.
d. Metering Requirements. The net energy output from a Fuel Cell Generation Unit
shall be metered according to the specifications in the Department's Guideline on
Metering and Calculating the Energy Output of Eligible Fuel Cell Generation Units
and verified by an independent Third Party Meter Reader, as defined in Rule 2.5(j)
of the NEPOOL GIS Operating Rules and approved by the Department. The APS
Alternative Generation Attributes reported to the NEPOOL GIS by an independent
Third Party Meter Reader shall be the amount that is qualified for Alternative Energy
Attributes, as specified in 225 CMR 16.05. This amount will be inclusive of the
application of any multiplier provided in 225 CMR 16.05(1)(a)7.c.
8. Thermal Waste-to-energy. A Thermal Waste-to-energy Generation Unit may qualify
as an APS Alternative Generation Unit and shall be metered according to the
specifications in the Department's Guideline on Metering and Calculating the Useful
Thermal Output of Eligible Renewable Thermal Generation Units.
(b) Commercial Operation Date. With the exception of Thermal Waste-to-energy
Generation Units, an APS Alternative Generation Unit's Commercial Operation Date shall
be on or after January 1, 2008, however, for an APS Renewable Thermal Generation Unit,
the Commercial Operation Date shall be on or after January 1, 2015, and for a Fuel Cell
Generation Unit, the Commercial Operation Date shall be on or after January 1, 2017.
(c) Metering. Except as provided in 225 CMR 16.05(4)(b), the APS Alternative Generation
from a Generation Unit shall be verified by an independent verification system or person
participating in the NEPOOL GIS accounting system as an independent Third Party Meter
Reader, as defined in Rule 2.5(j) of the NEPOOL GIS Operating Rules, or any successor
rule, and approved by the Department. The APS Alternative Generation reported to the
NEPOOL GIS by a Third Party Meter Reader shall be the net amount that is qualified for
Alternative Energy Attributes, as specified in 225 CMR 16.05.
(d) Location. The Generation Unit must be located within the ISO-NE Control Area, except
where otherwise specified in 225 CMR 16.00, and subject to the limitations in 225 CMR
16.05(1)(d).
1. Off-grid Generation. If the Generation Unit produces Off-grid Generation, such Unit
must be located in Massachusetts.
2. Behind-the-meter Generation. If the Generation Unit is wired to the electrical system
on the End-use Customer's side of a retail electric meter, such Unit must be
interconnected to the electric grid in Massachusetts.
(e) Net Carbon Dioxide Emissions Rate. A Generation Unit that generates electricity shall
not exceed a net site carbon dioxide emissions rate equal to the average emissions rate of the
current average value for emitting locational marginal units as shown in the most recent
ISO-NE Electric Generator Air Emissions Report available in the same year in which an
SQA is submitted for the Generation Unit. In quantifying the net site carbon dioxide
emissions, the emissions attributable to any site fuel consumption displaced by the Useful
Thermal Energy generated by the Generation Unit is to be subtracted from the emissions due
to the direct consumption of fuel by the Generation Unit. The monitoring, calculation, and
reporting of the net carbon dioxide emissions rate shall be subject to verification by an
independent consultant acceptable to the Department and, in consultation with the MassDEP
and at the expense of the Unit's Owner or Operator. An APS Renewable Thermal Generation
Unit using Eligible Biomass Fuel shall not be subject to the net carbon dioxide emissions rate
in 225 CMR 16.06(1)(e), but instead subject to the net greenhouse gas emission requirement
in 225 CMR 16.06(4)(i).
(f) Eligibility of RPS Class I Renewable Generation Units, and RPS Class II Renewable
Generation Units. A Generation Unit that is qualified as an RPS Class I Renewable
Generation Unit pursuant to 225 CMR 14.00: Renewable Energy Portfolio Standard —
Class I or as an RPS Class II Renewable Generation Unit pursuant to 225 CMR
15.00: Renewable Energy Portfolio Standard – Class II may also be qualified as an APS
Alternative Generation Unit provided it meets all eligibility criteria in 225 CMR 16.00.
(g) Reclassification of APS Alternative Generation Units. An APS Alternative Generation
Unit that meets the eligibility to qualify more than one type of APS Alternative Generation
Unit shall only qualify as one type of APS Alternative Generation Unit, which the Owner
shall designate in its Statement of Qualification Application. An APS Alternative
Generation Unit shall have the option to switch the type of APS Alternative Generation Unit
for which it has received a Statement of Qualification one time during the duration of its
qualification period.
(2) Co-firing Waiver. A portion of the electrical energy or Useful Thermal Energy output of
a Generation Unit that uses an APS Ineligible Energy Source with another fuel may qualify as
APS Alternative Generation provided the Generation Unit meets the eligibility requirements of
225 CMR 16.05, subject to the limitations in 225 CMR 16.05(2).
(a) The percentage of the total electrical energy or Useful Thermal Energy output that
qualifies as APS Alternative Generation in a given time period shall be equal to one minus
the ratio of the net heat content of the APS Ineligible Energy Source consumed to the net heat
content of all fuel consumed in that time period.
(b) If co-firing an APS Ineligible Energy Source with another fuel, the entire Generation
Unit must demonstrate to the satisfaction of the Department in consultation with the
MassDEP that the Unit meets or will meet the emission performance standards, including the
net carbon dioxide emissions rate, that are or would be required by the MassDEP for
comparably-fueled Units within Massachusetts, including the standards specified for the
technology type of the Unit as set forth in 225 CMR 16.05(1)(a) and (e). The Department
may require the Generation Unit Owner or Operator to retain at its own expense a third-party
consultant deemed satisfactory to the Department, to provide DOER and the MassDEP with
assistance in determining whether this criterion is or will be met by the Unit.
(c) The Generation Unit must provide a fuel supply plan that specifies each and every fuel
that it intends to use, in what relative proportions in co-firing, and with what individual input
heat values. Such plan shall include the procedures by which the Unit will document to the
satisfaction of the Department its compliance with the plan.
(d) The provisions of 225 CMR 16.05(2) shall not apply to the incidental use of an APS
Ineligible Energy Source solely for the purpose of cold starting a Generation Unit that
otherwise exclusively uses other fuels.
(3) Special Provisions for Aggregations. An Aggregation of Generation Units that are located
behind the customer meter or that are Off-grid Generation Units, each of which could
independently meet the relevant requirements of 225 CMR 16.05, may receive a single SQ and
be treated as a single APS Alternative Generation Unit under the following criteria and
procedures:
(a) Each Generation Unit in such Aggregation must use the same technology as all other
Units in the Aggregation.
(b) Each of the Owners or Operators of Generation Units within the Aggregation must enter
into an agreement with a person or entity that serves as the Authorized Agent for the
Aggregation in all dealings with the Department and with the NEPOOL GIS, and such
agreement must include procedures by which the electrical energy output and, in the case of
a CHP Unit, the Useful Thermal Energy output and fuel input, of each Unit shall be
monitored and reported to the NEPOOL GIS.
(c) The Authorized Agent of the Aggregation must establish and maintain a Generator
account at the NEPOOL GIS under the NEPOOL GIS Operating Rules, including all
provisions for Non-NEPOOL Generator Representatives, as that term is defined in Rule
2.1(a)(vi) of the NEPOOL GIS Operating Rules.
(d) The electrical energy output, or the Alternative Energy Attribute qualified portion of
such output as provided in 225 CMR 16.05(1)(a)2.a., 225 CMR 16.05(1)(a)3., or 225 CMR
16.05(1)(a)6., of each of the Generation Units in the Aggregation must be individually
monitored and recorded, and it must be reported to the NEPOOL GIS as part of an
aggregated total for the Aggregation, by an independent Third Party Meter Reader as defined
in Rule 2.5(j) of the NEPOOL GIS Operating Rules.
(4) Special Provisions for APS Renewable Thermal Generation Units. A Generation Unit that
meets the eligibility provisions under 225 CMR 16.05(1)(a)6., shall be subject to the following
provisions:
(a) Size Classification. APS Renewable Thermal Generation Units shall be classified as
small, intermediate, or large based on the rated capacity of the system. If an APS Renewable
Thermal Generation Unit consists of several individual and separate units, the individual
unit's capacities shall be summed and the total capacity will be considered against the size
threshold. In the case of a combination of solar thermal technologies and other technologies,
the thresholds shall be applied separately to the solar and non-solar units. APS Renewable
Thermal Generation Unit size classifications are as follows:
Classification
Small
Intermediate
Large
AEC calculation
basis
Calculated net
renewable
thermal output
Calculated net
renewable thermal
based on indirect
metering
Calculated net
renewable
thermal output
based on direct
metering of fuel
input
Metered net
renewable thermal
output
Solar thermal:
evacuated tube
and flat plate solar
hot water
Collector surface
area less than or
equal to 660 sq ft
Collector surface
area between
660 and 4,000 sq ft
-
Collector surface
area greater than or
equal to 4,000 sq ft
Solar thermal:
solar hot air
-
Collector surface
area less than or
equal to 10,000 sq ft
-
Collector surface
area greater than
10,000 sq ft
Solar sludge dryer
-
-
-
All
Eligible Biomass
Fuel
-
-
Capacity less than
or equal to
1,000,000 Btu per
hour
Capacity greater
than 1,000,000 Btu
per hour
Compost heat
exchange system
-
-
-
All
Air source heat
pump: electric
motor or engine
driven
Output capacity
less than or equal
to 134,000 Btu per
hour
-
Output capacity
between 134,000
and 1,000,000 Btu
per hour
Output capacity
greater than or equal
to 1,000,000 Btu per
hour
Ground source
heat pump
Output capacity
less than or equal
to 134,000 Btu per
hour
-
Output capacity
between 134,000
and 1,000,000 Btu
per hour
Output capacity
greater than or equal
to 1,000,000 Btu per
hour
Deep geothermal
-
-
-
All
Small Generation Units shall have the option to be classified as either intermediate or
large Generation Units if they wish to forgo pre-minting and instead meter their Useful
Thermal Energy as required by the Guideline on Metering and Calculating the Useful
Thermal Output of Eligible Renewable Thermal Generation Units - Part 2 (Metering for
Intermediate and Large Generation Units). Intermediate Generation Units shall also have
the option to be classified as large Generation Units if they wish to meter their Useful
Thermal Energy as required by the Guideline on Metering and Calculating the Useful
Thermal Output of Eligible Renewable Thermal Generation Units - Part 2 (Metering for
Intermediate and Large Generation Units). Generation Units which opt to change their size
classification must notify the Department in their Statement of Qualification Application and
must remain their chosen size classification for the duration of their qualification period.
(b) Metering Requirements. The net Useful Thermal Energy output from an APS
Renewable Thermal Generation Unit shall be metered according to the specifications in the
Department's Guideline on Metering and Calculating the Useful Thermal Output of Eligible
Renewable Thermal Generation Units and verified by an independent Third Party Meter
Reader, as defined in Rule 2.5(j) of the NEPOOL GIS Operating Rules and approved by the
Department. The APS Alternative Generation Attributes reported to the NEPOOL GIS by
an independent Third Party Meter Reader shall be the amount as specified in 225 CMR
16.05(1)(a)6.b. This amount will be inclusive of any netting of energy use by the APS
Renewable Thermal Generation Unit as prescribed in 225 CMR 16.05(1)(a)6.b.iii., and the
application of any multiplier in the Department’s Guideline on Multipliers for Renewable
Thermal Generation Units.
1. An APS Renewable Thermal Generation Unit that uses more than one eligible
technology in 225 CMR 16.05(1)(a)6.a. is required to use the same independent Third
Party Meter Reader for all technologies.
2. Each APS Renewable Thermal Generation Unit is required to have its own individual
NEPOOL GIS asset. An APS Renewable Thermal Generation Unit that uses more than
one eligible technology in 225 CMR 16.05(1)(a)6.a. is required to have a NEPOOL GIS
asset for each technology. APS Renewable Thermal Generation Units that utilize the
same technology and are located in the same state may qualify as an Aggregation and
share a NEPOOL GIS asset.
3. An APS Renewable Thermal Generation Unit that meets the criteria of a small
Generation Unit or an intermediate as prescribed in 225 CMR 16.05(1)(b)(ii) shall be
exempt from the metering requirements in 225 CMR 16.05(4)(b) and, instead, be subject
to the Small and Intermediate Generation Unit Annual Net Useful Thermal Energy
Determination in 225 CMR 16.05(4)(c).
(c) Small and Intermediate Generation Unit Annual Net Useful Thermal Energy
Determination. An APS Renewable Thermal Generation Unit that meets the criteria of a
small or intermediate Generation Unit as prescribed in 225 CMR 16.05(4)(a) may have its
annual net Useful Thermal Energy generation output determined by a formula or
methodology as prescribed in the Department's Guideline on Metering and Calculating the
Useful Thermal Output of Eligible Renewable Thermal Generation Units. This
approximation shall be a reasonable determination by the Department to estimate the net
Useful Thermal Energy delivered by the APS Renewable Thermal Generation Unit,
specifically considering the APS Renewable Thermal Generation Unit's capacity,
performance characteristics, and load application being served. The MassCEC will act as
the independent verifier for all small Generation Units and intermediate Generation Units
using Eligible Biomass Woody Fuel, and will deploy appropriate and reasonable measures
to verify ongoing operation of the small Generation Units in line with their estimated net
Useful Thermal Energy generation.
(d) Pre-minting of APS Alternative Generation Attributes for Small APS Renewable
Thermal Generation Units. An APS Renewable Thermal Generation Unit that meets the
criteria of a small Generation Unit as prescribed in the Department's Guideline on Metering
and Calculating the Useful Thermal Output of Eligible Renewable Thermal Generation Units
may be provided all of its APS Alternative Generation Attributes as follows, the APS
Renewable Thermal Generation Unit may have all of the APS Alternative Generation
Attributes in 225 CMR 16.05(4)(c) pre-minted as APS Alternative Generation Attributes,
and may be minted in the first quarter after the APS Alternative Generation Unit's Statement
of Qualification or Commercial Operation Date, whichever is later. The volume of
pre-minted APS Alternative Generation Attributes shall be equal to 40 times the quarterly
volume of the monthly Attributes determined in 225 CMR 16.05(4)(c).
(e) Eligibility Criteria for Small Air Source Heat Pumps. All small air source heat pump
Renewable Thermal Generation Units, as prescribed in 225 CMR 16.05(4)(a), must meet all
of the following requirements:
1. be ENERGY STAR™ certified;
2. meet the Cold Climate Air Source Heat Pump Specification (Version 2.0) published
by Northeast Energy Efficiency Partnerships effective January 1, 2017 or any version
thereafter;
3. have a variable speed compressor;
4. be part of an Air Conditioning, Heating, and Refrigeration Institute matched system;
and
5. have a coefficient of performance greater than or equal to 1.9 at 5°F and a coefficient
of performance greater than or equal to 2.5 at 17°F.
For new construction, the small air source heat pump Renewable Thermal Generation
Unit must supply 100% of the building's total annual heating and cannot have any
supplemental, non-renewable heating sources. In retrofit construction or existing buildings,
all small air source heat pump Renewable Thermal Generation Units that do not meet the
above requirement must be used as the primary source of heat, supply at least 90% of the
total annual heating, be integrated to a heating distribution system, capable of distributing
produced heat to all conditioned areas of the building, and have a heat-rate capacity at five
degrees Fahrenheit that is at least 50% of the nameplate capacity of the existing heating
source equipment.
(f) Eligibility Criteria for Small Ground Source Heat Pumps. All small ground source heat
pumps Renewable Thermal Generation Units, as prescribed in 225 CMR 16.05(4)(a), must
meet the following requirements:
1. be certified to the International Organization for Standards Standard 13256-1
Water-source heat pumps — Testing and rating for performance — Part 1: Water-to-air
and brine-to-air heat pumps, 1998 or the International Organization for Standards
Standard 13256-2 Water-source heat pumps — Testing and rating for performance —
Part 2: Water-to-water and brine-to-water heat pumps, 1998;
2. have American Heating and Refrigeration Institute rated operating coefficient of
performance and operating energy efficiency ratio equal to or greater than the following:
Small Ground Source Heat
Pump System Type
Cooling Energy Efficiency
Ratio
Heating Coefficient of
Performance
Closed loop water to air
Open loop water to air
Closed loop water to water
Open loop water to water
3. be installed by licensed contractors and/or plumbers in accordance with the National
Electric Code and manufacturer's specifications and must conform to all applicable
municipal, state, and federal codes, standards, regulations, and certifications, as well as
program requirements;
4. have blowers that are multi-speed or variable-speed, high-efficiency motors. Motors
qualify as energy-efficient if they meet or exceed the efficiency levels listed in the
National Electric Manufacturers Association's MG1-1993 publication;
5. use compressors that are two-stage, multi-speed, or variable-speed drives, unless they
are water-to-water units. Single-stage water-to-water systems are eligible, provided they
include accumulator tanks with the greater of ten gallons of capacity per heating ton or
industry/manufacturer recommended best practice;
6. for vertically bored closed-loop systems, Generation Units must have a minimum
depth of 150 feet per 12,000 Btu per hour of heating load served by the system;
7. all closed-loop bore grouting must have a grout conductivity equal to or greater than
anticipated earth conductivity of the drill site up to one Btu per hour-foot-degree
Fahrenheit;
8. have at least 15 feet of separation between closed-loop bore holes;
9. must comply with MassDEP Bureau of Resource Protection Drinking Water
Program, Guidelines For Ground Source Heat Pump Wells, and Underground Injection
Control Program, December 2013;
10. all open-loop system wells shall be installed in conformance with MassDEP's
Private Well Guidelines or MassDEP's Guidelines and Policies for Public Water
Systems, whichever is applicable;
11. all system wells shall be installed in conformance with 313 CMR 3.00: Registration
of Well Drillers and Filing of Well Completion Reports;
12. standing column wells must include bleed circuits and drywells to maximize
thermal efficiency based on available water production;
13. all systems must supply 100% of a building's total annual heating; non-renewable
supplemental heat sources are prohibited; and
14. all closed loop systems must be installed and tested in accordance with subsections
4 and 5 in section 1 of the Closed-Loop/Geothermal Heat Pump Systems, Design and
Installation Standards, published by the International Ground Source Heat Pump
Association, dated 2017. In lieu of the pressure testing described in subsection five in
section one of the above-referenced standard, closed loop systems shall be hydrostatically
pressure tested in accordance with ASTM Standard F2164 using the test pressure
specified by the design engineer for the system.
(g) Restrictions and Standards on the Use of Eligible Biomass Woody Fuel. An APS
Renewable Thermal Generation Unit using Eligible Biomass Woody Fuel is subject to the
following restrictions:
1. Feedstock Requirements. An APS Renewable Thermal Generation Unit using
Eligible Biomass Woody Fuel must use a minimum percentage of Eligible Biomass
Woody Fuel derived from Forest Derived Residues, Forest-derived Thinnings, Forest
Salvage, or residues derived from wood products manufacturing consisting of Clean
Wood, as defined in the definition of eligible woody biomass fuel in 225 CMR 16.03.
The Department shall set the minimum feedstock requirement in the Department's
Guideline on Biomass, Biogas, and Biofuel for Eligible Renewable Thermal Generation
Units.
2. Fuel Quality and Unit Control Device Requirements. Generation units shall meet at
least one of the following fuel quality specifications:
a. A boiler or furnace of less than 3,000,000 Btu per hour rated heat input that
utilizes an emission control device (e.g., electrostatic precipitator), subject to the
approval of the Department in consultation with MassDEP, does not have to meet the
fuel quality specifications in 225 CMR 16.05(4)(g)2.b. The emissions control device
shall be designed and operated to ensure that the boiler or furnace does not exceed
the applicable particulate matter emission limit in 225 CMR 16.05(4)(g)5.
b. A boiler or furnace of less than 3,000,000 Btu per hour rated heat input that does
not utilize an emission control device (e.g., electrostatic precipitator) must meet the
following fuel quality specifications:
Fuel Quality Specifications
Pellets
Chips
Calorific value
Greater than 8,000 Btu
per pound
Greater than or equal to
5,500 Btu per pound
Moisture
Less than or equal to 8%
Less than or equal to 35%
Ash content by weight
Less than or equal to 1%
Less than or equal to 1.5%
Chip size (percent retained by a ½
inch mesh screen)
Not applicable
75% or adhere to
manufacturer’s protocol
Chlorides
Less than or equal to
300 parts per million
Not applicable
c. A boiler or furnace of equal to or greater than 3,000,000 Btu per hour rated heat
input must receive a MassDEP plan approval pursuant to 310 CMR 7.02(5), which
shall dictate fuel quality specifications.
3. Sustainable Forestry Management. Forest Derived Residues and Thinnings shall only
be sourced from forests meeting Sustainable Forestry Management practices, as
independently verified through the attestation of a licensed forester, certified forester, or
independent certification.
4. System Performance. APS Renewable Thermal Generation Units shall meet fuel
conversion efficiency and performance standards achievable by best-in-class
commercially-feasible technologies, identified in the following table:
Performance Requirement
Pellets
Chips
Thermal efficiency at nominal
output
Greater than or equal to
85% Higher Heating
Value
Greater than or equal to
75% Higher Heating Value
or
Greater than or equal to
80% Lower Heating Value
if EN303-5 is used to
verify particulate emissions
Start up
Adhere to manufacturer’s ignition protocol
Modulation/shut off
The system must automatically modulate to lower
output and/or turn itself off when the heating load
decreases or is satisfied
Pressurized portion of the
system
Compliant with 522 CMR 4.00: Heating Boilers and
Other Heat Storage Sources
Thermal storage
Required, unless an exception is issued by the
Department
Fuel storage
The system must have covered bulk storage
Feedstock conveyance
The system must be automatically fed from feedstock
storage to the furnace or boiler
5. Thermal Storage. Generation Units shall minimize any significant deterioration of
efficiency or air emissions performance due to cycling by applying correctly sized and
insulated thermal storage. Thermal storage shall meet the following size thresholds:
Lead Boiler System Size
(Heat Input)
Thermal Storage Required
Less than 80,000 Btu per hour
80 gallons
Between 80,000 Btu per hour and
119,000 Btu per hour
one gallon per 1,000 Btu
per hour
Between 119,000 Btu per hour and
1,000,000 Btu per hour
119 gallons
Greater than 1,000,000 Btu
per hour
two gallons per 1,000 Btu
per hour
An Owner or Operator of a Generation Unit may apply for an exception from the
requirements in 225 CMR 16.05(4)(g)4. if it can demonstrate to the Department that an
inclusion of thermal storage would deteriorate the efficiency or air emissions
performance of the Generation Unit, or the system can maintain efficiency and air
emission performance at low capacity without thermal storage.
6. Emission Performance Standards. APS Renewable Thermal Generation Units shall
meet air emission performance standards that are protective of public health, including
standards for particulate matter sized 2.5 microns or less and carbon monoxide, as
identified in the following table:
A boiler or furnace of less than 3,000,000 Btu per hour rated heat input must meet the
applicable emission limits below:
Pollutant
Pellets/liquid biofuels/biogas
Chips
Particulate Matter
No more than 0.08 lb PM
input
per 1,000,000 Btu
or
No more than 0.03 lb PM
per 1,000,000 Btu input at
sensitive populations
No more than 0.10 lb PM per
input
1,000,000 Btu
or
No more than 0.05 lbs total PM
input
per 1,000,000 Btu
if
EN303-5 is used to verify
emissions
or
No more than 0.03 lb PM per
input
1,000,000 Btu
at sensitive
populations
Carbon monoxide
No more than 270 parts per
million at 7% oxygen
No more than 270 parts per
million at 7% oxygen
A boiler or furnace of greater than or equal to 3,000,000 Btu per hour rated heat
input:
Particulate matter,
carbon monoxide, and
other relevant criteria
pollutants
MassDEP plan approval required, pursuant to 310 CMR 7.02(5).
For the purpose of 225 CMR 16.05(4)(f)5., sensitive populations include schools,
hospitals, nursing homes, or additional facilities determined by the Department.
7. Verification of Eligible Biomass Woody Fuel. In order to verify the use of Eligible
Biomass Woody Fuel, an APS Renewable Thermal Generation Unit shall report the
following to the Department on a quarterly basis:
a. Supplier of the fuel;
b. Amount of fuel delivered;
c. Date of delivery; and
d. Fuel quality specifications prescribed in 225 CMR 16.05(4)(g)1., including a
certification that any emission control device was operated and maintained in
accordance with the manufacturer's specifications in order to comply with the
applicable particulate matter emission limit in 225 CMR 16.05(4)(g)5.
The Department will review the Department's Guideline on Biomass, Biogas, and
Biofuels for Eligible Renewable Thermal Generation Units every two years in
consultation with the MassDEP and DCR and update the Guideline where appropriate.
The Department will assess the impact of biomass heating on the region's forests in 2018
and 2020, as well as every five years thereafter in coordination with the Forest Impact
Assessment under the Renewable Portfolio Standard Class I, as prescribed in 225 CMR
14.06(8)(b)2., and make changes as necessary. The Department will report annually on
the aggregate woody biomass fuel
(h) Aggregation of Units using Eligible Liquid Biofuels. An APS Renewable Thermal
Generation Unit using Eligible Liquid Biofuels or Eligible Liquid Biofuels blended with
heating oil shall seek qualification as an APS Renewable Thermal Generation Unit only as
part of an Aggregation, as provided for in 225 CMR 16.05(3).
(i) Greenhouse Gas Emission Reduction. APS Renewable Thermal Generation Units
utilizing biomass, biogas, or biofuel shall reduce life-cycle greenhouse gas emissions by at
least 50% compared to a high-efficiency unit utilizing the fuel that is being displaced or for
a new load, a high-efficiency natural gas unit, if natural gas is available at reasonable cost to
the site, or otherwise, the fuel that is most likely to be utilized. The procedures for
calculating whether a Generation Unit meets the 50% reduction can be found in the
Department's Guideline on Biomass, Biogas, and Biofuels for Eligible Renewable Thermal
Generation Units and in the Department's Guideline on Reduction of Greenhouse Gases for
Eligible Renewable Thermal Generation Units Using Eligible Woody Biomass. Generation
Units that report a percent under-compliance in 225 CMR 16.05(4)(i), shall be placed in a
probationary status and the Department shall notify the Owner that its Statement of
Qualification shall be revoked at the end of five Compliance Years following the Compliance
Year for which the percent under-compliance was reported. The Generation Unit's
probationary status shall be rescinded and the Generation Unit's Statement of Qualification
shall no longer be subject to revocation if either:
1. for any three Compliance Years of the probationary period the Generation Unit
demonstrates that it is complying with the lifecycle greenhouse gas emissions
requirements; or
2. the Generation Unit's accumulated percent under-compliance is offset by any net
over-compliance with the lifecycle greenhouse gas emissions requirement during the
probationary period.
(j) Cap on the Available Number of Attributes for Generation Units Using Eligible Liquid
Biofuel.
1. In each Compliance Year the total number of Attributes minted to Generation Units
using Eligible Liquid Biofuel may not exceed 20% of the total projected annual
compliance obligation for the Compliance Year, in which they are generated, with no
more than 10% of the Attributes generated prior to July 1 . If 100% of the Attributes
st
available prior to July 1 are not allocated, the remaining number of available Attributes
st
shall be rolled over and allocated during either of the remaining quarters in that calendar
year. If the number of Attributes reported by Generation Units exceeds the available
Attributes, the number of available Attributes shall be allocated on a pro-rata basis.
2. The Department shall estimate the compliance obligation by multiplying the
Minimum Standard percentage by the total MWh of electrical energy sales by Retail
Electricity Suppliers to End-use Customers in the Compliance Year two years prior. The
Department shall calculate the annual and per quarter number of Attributes available for
Generation Units using Eligible Liquid Biofuel in a given Compliance Year no later than
August 31 of the preceding Compliance Year. The Department shall publish this
st
information on its website at
www.mass.gov/orgs/massachusetts-department-of-energy-resources.
(k) Eligible Biomass Woody Fuel Suppliers List. The Department shall establish and
maintain a list of suppliers of Eligible Biomass Woody Fuel on its website at
www.mass.gov/orgs/massachusetts-department-of-energy-resources. Any fuel supplier
wishing to be included on the Department's list must complete the application provided on
the Department's website at
www.mass.gov/orgs/massachusetts-department-of-energy-resources. Suppliers will be
classified into one of three classes based on the percentage of residues contained in the fuel
distributed to Generation Units and the fuel being displaced by the Generation Unit, as
follows:
Class
Fuel Being Displaced
Minimum Combined
Percentage of Forest Derived
Residues, Non-forest Derived
Residues, and Forest Salvage
Class I
Natural gas, electric resistance,
propane, fuel oil #6, fuel oil #2
55%
Class II
Electric resistance, propane, fuel oil
#6, fuel oil #2
50%
Class III
Fuel oil #6, fuel oil #2
35%
Upon qualification, Generation Units will be notified by the Department which fuel class
they must purchase when sourcing fuel from a supplier on the Department's Biomass
Suppliers List. Any Generation Unit that desires to purchase fuel from a supplier not on the
Department's Biomass Suppliers List may request approval from the Department and shall
be required to provide additional information. Generation Units displacing an existing
biomass system shall have their fuel class determined by the Department.
(l) Eligible Liquid Biofuel Suppliers List. The Department shall establish and maintain a
list
of
suppliers
of
Eligible
Liquid
Biofuel
on
its
website
at
www.mass.gov/orgs/massachusetts-department-of-energy-resources. A fuel supplier must
complete and submit an application to the Department to be included on the Department's
Eligible Liquid Biofuel suppliers list. Fuel suppliers must be registered in the Environmental
Protection Agency's Renewable Fuel Standard (RFS2), 40 CFR §§ 80.1400 through 80.14.74,
and must verify that they produce biodiesel from organic waste feedstocks. Fuel suppliers
may be required to provide documentation to the Department after being added to the list in
order to demonstrate continued compliance.