248 CMR 5.07
Modifications to Chapter 7, Gas Piping Installation
(1) Replace section 7.1.6 with the following:
7.1.6 Piping Underground Beneath Buildings. When the installation of gas piping underground
beneath buildings is unavoidable, the piping shall be encased in a vented conduit that is listed,
certified by the manufacturer, or designed by a professional engineer to be capable of
withstanding the imposed load and influences of the underground environment.
(a) Conduit Ventilation.
1. Conduit vents shall be sized no less than 50% of the conduit.
2. Conduit vents shall terminate at the exterior of the building or structure, be a
minimum of four feet above finished grade, and shall be installed so as to prevent the
entrance of water and insects.
(b) Undiluted Liquefied Petroleum Gas. Undiluted Liquefied Petroleum Gas shall not be
conveyed in piping and through this type of conduit due to the characteristics and behavior
properties of this gas.
(2) Add the following to the end of sub-section 7.2.5.4
Supports added for piping on rooftops must be installed in such a manner that they do not
compromise the integrity of the roof. However, should the performance of gas-fitting work
impact the structural integrity of roofing components, necessary corrective work falls outside the
scope of this code. See 780 CMR: Massachusetts Amendments to the International Building
Code 2009 or 271 CMR: Board of Examiners of Sheet Metal Workers, if applicable, for
licensing and other requirements for said work.
(3) Add a new sub-section 7.3.4.1 as follows:
7.3.4.1 CSST Tubing in Partitions. CSST installed vertically and horizontally in concealed wall
spaces or partitions shall be protected in accordance with Table 7.3.4.1:
Table 7.3.4.1
Protection of CSST Tubing Installed in Concealed Wall Spaces and Partitions
Tubing Orientation
and Location
Insulation Type
Tubing Size less than
one inch
Tubing Size equal to or
greater than one inch
Vertical Wall
None
1. Single runs only.
2. Tubing not secured to
structure.
3. CSST manufacturer
specified strike plates at points
of penetration.
4. CSST Strike plates on both
sides of wall.
Same as CSST less than
one inch with CSST
manufacturer specified
shielding device along
entire length in concealed
space.
Table 7.3.4.1 (continued)
Protection of CSST Tubing Installed in Concealed Wall Spaces and Partitions
Tubing Orientation
and Location
Insulation Type
Tubing Size less than
one inch
Tubing Size equal to or
greater than one inch
Vertical Wall
Non-rigid
1. Single runs only.
2. Tubing not secured to structure.
3. Tubing installed between insulation and wall board.
4. CSST manufacturer specified strike plates at points of
penetration
Vertical Wall
Rigid
Schedule 40 pipe or CSST manufacturer specified shielding
device along entire length and at points of penetration.
Horizontal Wall
N/A
CSST manufacturer specified
shielding device along length
between studs and strike plates
at points of penetration on both
sides of wall.
Same as CSST less than
one inch with CSST
manufacturer specified
shielding device along
entire length in concealed
space.
(4) Replace sub-section 7.9.2.4 with the following:
7.9.2.4 Emergency and Other Shutoff Valves for Laboratories. Each laboratory room or space
containing a gas outlet installed on tables, benches, or in hoods in educational, research,
commercial, and industrial occupancies shall have an emergency shutoff valve through which
all gas outlets are supplied. The emergency shutoff valve must be in a readily accessible space
adjacent to the laboratory's egress door and identified as such. Additional non-emergency shutoff
valves shall be provided in an accessible location for each individual table, bench, or hood
equipped with gas outlets.
7.13.2 CSST. CSST systems shall be bonded in accordance with subsection 7.13.1 unless such
bonding would be in conflict with manufacturer installation instructions. However, to the extent
the manufacturer's installation instructions require additional bonding which falls within the
scope of electrical licensure, this code shall not govern such requirements. In such instances, the
installation may not be approved by a plumbing or gas inspector unless there is proof that an
electrical permit has been obtained to perform such bonding.