248 CMR 5.09
Modifications to Chapter 9, Appliance, Equipment, and Accessory Installation
(1) Delete sub-section 9.1.1* and replace it with the following:
9.1.1* Appliances, Equipment, and Accessories to be Approved.
Board Required Product Acceptance. Only products and materials that meet the product
acceptance requirements of 248 CMR 3.04(1): Board Required Product-acceptance may be
utilized in gas fitting work in Massachusetts unless the Board has waived the necessity for
product acceptance per 248 CMR 3.04(1)(h).
(3) Delete sub-section 9.1.1.3 and replace with the following:
9.1.1.3 Unlisted Appliances, Equipment, and Accessories. Acceptance of unlisted gas
appliances, equipment, and accessories shall require a variance by the Board.
(5) Add a new sub-section 9.1.19.1 as follows:
9.1.19.1 Vent Lines.
(a) Vent lines shall be steel, wrought iron pipe, or corrugated stainless steel tubing (CSST).
Vents shall be:
1. sized as specified in this section; and
2. run to the outside of the building or structure using the shortest practical route and
shall not be trapped or installed in a manner that restricts air flow.
(b) Vent Lines shall be supported in accordance with subsection 7.2.5.
(c) Vent lines that terminate outside a building or structure shall be located no less than:
1. four feet away from any building opening or air intake; and
2. ten feet away from forced air intakes.
(d) Vent lines that penetrate roofs and sidewalls shall be run through metallic sleeves that
are sealed from the weather and insects, and:
1. extend no less than 18 inches above a roof surface when penetrating the roof or:
2. terminate through the sidewall to a safe location.
(e) CSST vent lines shall not penetrate roofs or sidewalls and shall transition to steel,
wrought iron pipe no less than one foot inside the building or structure.
(f) Appliance pressure regulators shall not be connected to a common manifold.
TABLE 9.1.19.1
Minimum Schedule 40 Pipe Size/CSST for
Venting of Gas Components
Gas Components
Maximum lengths of iron pipe or corrugated stainless steel tubing
(CSST) from components to outside the building
0 - 40 feet
0 - 100 feet
0 - 200 Feet
Main Gas Pressure Regulator
- Steel Pipe Size
- CSST Size (Low Pressure
Gas only)
¾ inch IPS
30/31 EHD
1 inch IPS
37 EHD
1¼ inch IPS
46/48 EHD
High & Low Gas Pressure
Switches When Manifolded
- Steel Pipe Size
- CSST Size (Low Pressure
Gas only)
¾ inch IPS
30/31 EHD
1 inch IPS
37 EHD
1½ inch IPS
60/62 EHD
TABLE 9.1.19.1 (continued)
Minimum Schedule 40 Pipe Size/CSST for
Venting of Gas Components
Gas Components
Maximum lengths of iron pipe or corrugated stainless steel tubing
(CSST) from components to outside the building
0 - 40 feet
0 - 100 feet
0 - 200 Feet
Block and Bleed Valves (when
used)
- Steel Pipe Size
- CSST Size (Low Pressure
Gas only)
Full IPS Relief
Increase
IPS/CSST one
Size
Increase IPS/CSST
two Sizes
9.1.22 Installation Instructions.
(a) The licensee shall conform to the equipment manufacturer's specific requirements in
completing an installation unless those requirements conflict with or are less stringent then
this code.
(b) The licensee shall also leave the manufacturer's installation, operating, and maintenance
instructions in a location at the premises where they will be readily available for reference
and guidance.
(c) When required by the Inspector, a copy of the manufacturer's installation, operating, and
maintenance instructions shall be provided within two working days prior to calling for a
final Inspection.
9.1.23 Carbon Monoxide Protection. No installation or replacement of a vented gas appliance
shall be permitted unless a battery powered or electrically hard wired carbon monoxide detector
is present on the same floor as the appliance or on the next adjacent floor when the appliance is
located in a crawl space unless the appliance is located in a detached, uninhabitable garage. For
all residential dwellings, a carbon monoxide detector must also be present on each habitable level
of the dwelling. These requirements shall not be deemed to waive any additional requirements
imposed by M.G.L. c. 148 § 26F½.
(8) Amend sub-section 9.2.1 by inserting the following at the end of the subsection:
Sufficient clearance must also be provided to allow the total replacement of the appliance or
equipment.
(9) Add a new sub-section 9.6.1.4 as follows:
9.6.1.4 General Requirements for Connectors.
(a) The maximum length of a connector shall not exceed 48 inches, however, this restriction
shall not apply to connectors utilized for a gas appliance subject to the provisions of
sub-section 9.6.1(4) or sub-section 9.6.1.1.
(b) A connector shall not be used for gas pressure in excess of 0.5 PSIG (14" water
column).
(c) A connector shall not be re-used except when used for disconnecting and reconnecting
the original gas equipment or appliance for servicing.
(10) Add a new sub-section 9.6.3.5 as follows:
9.6.3.5 Flexible gas hoses used to connect portable and mobile industrial appliances shall not
exceed a length of 20 feet.
(11) Amend sub-section 9.6.8 by inserting the following at the end of the subsection:
Such piping shall also be installed in a manner not to interfere with the total replacement of the
appliance or equipment.