R 408.10564
R 408.10564 Design of installation; equipment.
Cite as Mich. Admin. Code R 408.10564
Rule 564. (1) The requirements of this rule apply to equipment that is part of a
powered platform installation, such as any of the following:
(a) Platforms.
(b) Stabilizing components.
(c) Carriages.
(d) Outriggers.
(e) Hoisting machines.
(f) Wire ropes.
(g) Electrical components.
(2) Equipment installations shall be designed by, or under the direction of, a
registered professional engineer who is experienced in such design.
(3) The design shall provide for a minimum live load of 250 pounds (113.6 kg) for
each occupant of a suspended or supported platform.
(4) Equipment that is exposed to wind when not in service shall be designed to
withstand forces generated by winds that have a velocity of at least 100 miles per hour
(44.7 m/s) at 30 feet (9.2 m) above grade.
(5) Equipment that is exposed to wind when in service shall be designed to
withstand forces generated by winds that have a velocity of at least 50 miles per hour
(22.4 m/s) for all elevations.
(6) Bolted connections shall be self-locking or shall otherwise be secured to prevent
the loss of the connections by vibration.