R 408.10569 Electrical requirements.
Cite as Mich. Admin. Code R 408.10569
Rule 569. The following electrical requirements apply to buildings that utilize
working platforms for building maintenance:
(a) General building electrical installations shall be in compliance with the
provisions of General Industry Safety Standard Part 39 “Design Safety Standards for
Electrical Systems," as referenced in R 408.10509.
(b) Building electrical wiring shall be of such capacity that when a full load is
applied to the equipment power circuit not more than a 5% drop from building
service-vault voltage will occur at any power circuit outlet that is used by equipment
regulated by these rules.
(c) The equipment power circuit shall be an independent electrical circuit that
remains separate from all other equipment within or on the building, other than power
circuits that are used for hand tools which will be used in conjunction with the
equipment. If the building has an emergency power system, the equipment power circuit
may also be connected to this system.
(d) The power circuit shall be provided with a disconnect switch that can be locked
in the "off" or "on" position. The switch shall be located to allow the operators of the
equipment access to the switch.
(e) The disconnect switch for the power circuit shall be locked in the "on" position
when the equipment is in use.