Rule 675. (1) A swinging stair section shall not be used for a fire escape stairs,
except where termination is over a sidewalk, alley, or driveway.
(2) A swinging stair section shall not be located over doors, over the path of travel
from another exit, nor be in any location where there are obstructions.
(3) The width of a swinging stair section shall be at least equal to that of the stairs
above and the pitch shall not be steeper than that of the stairs above.
(4) A counterweight shall be provided for a swinging stair section and this shall be
of the type balancing about a pivot, no cables being used. Counter-balancing shall be
such that a weight of 150 pounds 1 step from pivot will not start swinging section, and a
weight of 150 pounds, 1/4 of the length of the swinging stairs from the pivot, will
positively cause the stairs to swing down.
(5) A latch or other device shall not be installed or used to lock a swinging stair
section in the up position.