R 408.10833
R 408.10833 Installation.
Cite as Mich. Admin. Code R 408.10833
Rule 833. (1) An extinguisher shall be installed securely on a hanger, in a bracket,
or mounted in a cabinet unless it is wheeled type or cart mounted. A means shall be used
to indicate the location of an extinguisher mounted in a cabinet or on a shelf. The
extinguisher shall be placed so that the operating instructions face outward.
(2) An extinguisher having a gross weight of not more than 40 pounds shall be
installed so that the top is not more than 5 feet above the floor. An extinguisher having a
gross weight of more than 40 pounds, except a wheeled type or cart mounted
extinguisher, shall be installed so that the top is not more than 3 1/2 feet above the floor.
An extinguisher, except a wheeled type or cart mounted extinguisher, shall be installed so
that the bottom is not less than 4 inches from the floor.