R 408.10916
R 408.10916 Gravity, suction, and pressure tanks.
Cite as Mich. Admin. Code R 408.10916
Rule 916. (1) A gravity or suction water tank shall be maintained at the full water
level designed for fire protection purposes.
(2) The water and air in a pressure water tank shall be maintained at the designed
levels and pressures.
(3) The water in a gravity, suction, or pressure tank and risers shall be maintained
above freezing temperature. Where a heater is used, the water temperatures shall be
not more than 60 degrees Fahrenheit.
(4) A steel water tank shall be inspected not less than every 3 years for
deterioration and, when necessary, repairs made.
(5) A wooden water tank shall be inspected not less than every 2 years for
deterioration and, when necessary, repairs made.