R 408.10934
R 408.10934 Hose and hose connections.
Cite as Mich. Admin. Code R 408.10934
Rule 934. (1) Where a hose outlet is provided for use of employees, the hose length
shall not exceed 100 feet of approved 1 1/2 inch lined hose attached to the outlet.
Unlined hose may remain in use on existing systems provided it is serviceable.
Replacement shall be with approved lined hose. In extreme conditions or climates
where damage or deterioration may result, the hose may be stored in another location
provided it is readily available to be connected.
(2) Hose and hose outlets shall be within easy reach of a person standing on a
floor, unobstructed and conspicuously marked.
(3) Hose outlets shall be standardized having threads or adapters with threads
conforming to those used by the organized public fire department.
(4) A shut-off type nozzle shall be provided, except where unlined hose is still
approved. Nozzles shall be of an approved type and have a discharge coefficient not
exceeding 110 psi (7.5 bars).