R 408.10983
R 408.10983 Location.
Cite as Mich. Admin. Code R 408.10983
Rule 983. (1) A local fire alarm system shall be mounted in a location where the
system will not be activated by vibration or jarring.
(2) A manual fire alarm box shall be mounted permanently to a wall or post and
protected against physical damage.
(3) A manual fire alarm box shall be located so that the maximum distance on
each floor to a box will be not more than 200 feet. The box shall be unobstructed,
readily accessible, and in the regular path of travel to an exit. The location of the box
shall be identified by a sign or light visible from a distance of not less than 200 feet.