R 408.11232
R 408.11232 High-pressure oxygen manifolds.
Cite as Mich. Admin. Code R 408.11232
Rule 1232. (1) An oxygen high-pressure manifold shall be not more than 6,000
cubic feet, except as permitted in subrule (3) of this rule.
(2) More than 1 unit may be located in a room, but they shall be not less than 50
feet (16 meters) apart or separated by a noncombustible barrier not less than 5 feet
(1.6 meters) high having a fire resistance of 1/2 hour.
(3) An oxygen high-pressure manifold with an aggregate of more than 6,000
cubic feet (170 cubic meters approximately) shall be located outdoors in a
separate noncombustible building or, if located in a building that is otherwise
occupied, the manifold shall be located in a separate room of noncombustible
construction having a fire-resistance rating of 1/2 hour or in an area with no
combustible material within 20 feet (6.1 meters) of the manifold.
(4) An oxygen manifold or oxygen bulk supply system with a storage capacity
of more than 20,000 cubic feet (560 cubic meters), including unconnected reserves,
shall be as prescribed in R 408.11222(9).