R 408.11234
R 408.11234 Fuel gas manifolding.
Cite as Mich. Admin. Code R 408.11234
Rule 1234. (1) Fuel gas connected to 1 manifold inside a building shall have a
total gas capacity of not more than 3,000 cubic feet (85 cubic meters approximately)
or 11.8 cubic feet (.33 cubic meters) of liquefied gas, which is 735 pounds (333
kilograms) water capacity. More than 1 manifold unit may be located in a room, but
the manifolds shall be not less than 50 feet (16 meters) apart or be separated by a
noncombustible barrier not less than 5 feet (1.6 meters) high having a fire-resistance
rating of 1/2 hour.
(2) Fuel gas capacity on 1 manifold of more than 3,000 cubic feet (85 cubic
meters approximately) or 11.8 cubic feet (.33 cubic meters) of liquefied gas, which
is 735 pounds (333 kilograms) water capacity, is permissible in a separate room
or compartment, as specified in R 408.11222(8), or located outside the building.
(3) The pressure in the gas cylinders connected to, and discharged
simultaneously through, a common manifold shall be approximately equal.
(4) Manifolds shall be approved either separately for each component part or as
an assembled unit.