R 408.11244 Station outlets.
Cite as Mich. Admin. Code R 408.11244
Rule 1244. (1) A station outlet shall be equipped with a shutoff valve for each torch
supplied from it, designated VF and VO in FIGURE 1, located upstream of other station
outlet equipment.
(2) A station outlet shall be provided backflow prevention devices, designated as SF
and SO in FIGURE 1, at each station outlet, including those on a portable header, to
prevent backflow, except where pipeline protection equipment, designated as PF in
FIGURE 1, C is located at the station outlet.
(3) A station outlet shall terminate with an approved union connection for a regulator
or a hose, except that the outlet may terminate with pipe threads where a permanent
connection is made, such as to a machine.
(4) Each station outlet shall be equipped with a detachable seal outlet cap, secured in
place, which shall seal the outlet except when a hose, regulator, or piping is attached.
(5) The total volume of acetylene used per hour shall not exceed 1/7 of the total
volume of the acetylene supply in the system.
FIGURE 1
LEGEND:
PF
Protective equipment in fuel gas piping
VF
Fuel gas station outlet valve
VO
Oxygen station outlet valve
SF
Backflow prevention devices(s) at fuel gas station outlet
SO
Backflow prevention device(s) at oxygen station outlet