R 408.11274 Installation.
Cite as Mich. Admin. Code R 408.11274
Rule 1274. (1) The frame or case of a welding machine shall be grounded unless
the manufacturer does not recommend it.
(2) The work on which the operator welds shall be grounded by a grounded metal
floor, platen, connection to a grounded building frame, or by a direct ground to the
machine. A wire used for grounding a work piece shall be capable of carrying the full
welding current.
(3) A conduit containing an electrical conductor shall not be used for completing
a work-lead circuit.
(4) A pipeline in service shall not be used as a permanent part of a work-lead
circuit, but may be used during construction, extension, or repair if current is not
carried through threaded joints, flanged bolted joints, or caulked joints and if special
precautions are used to avoid sparking at connection of the work-lead cable.
(5) Chains, wire ropes, cranes, hoists, and elevators used for carrying loads shall
not be used to carry a welding current.
(6) A welding cable shall be protected against damage, entanglement, or contact
with power supply or high tension wires.
(7) A welding machine not provided with a controller or disconnect switch as
an integral part shall have a controller or disconnect switch with overload protection
provided. A disconnect switch with overload protection or overload disconnect
protection or equivalent shall be provided for each outlet used by a portable welding
machine.
(8) The rated current carrying capacity of the supply conductors for individual
machines shall be not less than the rated primary current for the welding machine. The
rated current carrying capacity of conductors for a group of welding machines may be
less than the sum of the rated primary currents of the welding machines supplied. The
conductor rating shall be determined in each case according to the machine loading
based on the use to be made of each welding machine and the allowance permissible if
all the machines supplied by the conductor will not be in use at the same time.
(9) Where a welding machine is working sufficiently close to another machine
so that a welding operator is likely to touch the exposed parts of more than 1
electrode holder simultaneously, the machine shall be connected so as to minimize
shock hazard as follows:
(a) DC machines shall be connected with the same polarity.
(b) AC machines shall be connected to the same phase of the supply circuit
and with the same instantaneous polarity.