R 408.11292 Stationary acetylene generators.
Cite as Mich. Admin. Code R 408.11292
Rule 1292. (1) An acetylene generator shall be installed level and in a manner not
to place a strain on the generator or its connections. A generator shall be
electrically grounded.
(2) A generator shall be located where water will not freeze. Heating shall be by
steam, hot water, or other indirect means. Open flames, fire, or other sources of ignition
shall not be permitted inside a generator house, room, or in any enclosure
communicating with them. Sodium chloride or other corrosive chemicals shall not be
used for protection against freezing.
(3) A water supply line to an acetylene generator with a noncontinuous
connection shall terminate not less than 2 inches (5.08 centimeters) above the fill
opening so that the water can be observed as it enters the generator. A supply line
with a continuous connection shall be used only when the generator is provided an
open overflow or an automatic water shutoff which will prevent overfilling the
generator.
(4) An acetylene generator shall discharge only through an open connection
into a vented outdoor receptacle or residue pit.
(5) Each generator shall be provided with a vent pipe of galvanized iron or steel. The
pipe shall be secured to the building without a trap and shall be installed so that
condensation will drain back to the generator.The pipe shall carry to outside the building
and shall terminate in a hood or bend not less than 12 feet from the ground and 3 feet
(.91 meters) from combustible construction, away from a window or other opening
in a building and any source of ignition, and shall be constructed so that rain, snow,
insects, or birds cannot obstruct the opening. The vent pipes from several generators
shall not be interconnected, but shall lead outside separately.