R 408.13389
R 408.13389 In-service care and use of electrical protective equipment.
Cite as Mich. Admin. Code R 408.13389
Rule 3389. (1) Electrical protective equipment shall be maintained in a safe, reliable
condition.
(2) The following specific requirements apply to rubber insulating blankets, rubber
insulating covers, rubber insulating line hose, rubber insulating gloves, and rubber
insulating sleeves.
(3) Maximum use voltages shall conform to those listed in Table D.
(4) An employer shall ensure that insulating equipment is inspected for damage
before each day’s use and immediately following any incident that can reasonably be
suspected of causing damage. Insulating gloves shall be given an air test, along with the
inspection.
Note to subrule (4): ASTM F-1236 “Standard Guide for Visual Inspection of
Electrical Protective Rubber Products,” 1996 Edition with 2012 supplement, as adopted
in R 408.13301a, presents methods and techniques for the visual inspection of electrical
protective equipment made of rubber. This guide also contains descriptions and
photographs of irregularities that can be found in this equipment.
(5) Insulating equipment with any of the following defects shall not be used.
(a) A hole, tear, puncture, or cut.
(b) Ozone cutting or ozone checking, that is, a series of interlacing cracks produced
by ozone on rubber under mechanical stress.
(c) An embedded foreign object.
(d) Any of the following texture changes:
(i) Swelling.
(ii) Softening.
(iii) Hardening.
(iv) Becoming sticky or inelastic.
(v) Any other defect that damages the insulating properties.
(6) An employer shall ensure that insulating equipment found to have other defects
that might affect its insulating properties is removed from service and returned for testing
under subrules (10) and (11) of this rule.
(7) An employer shall ensure that insulating equipment is cleaned as needed to
remove foreign substances.
(8) Insulating equipment shall be stored in a location and in a manner as to protect it
from all of the following:
(a) Light.
(b) Temperature extremes.
(c) Excessive humidity.
(d) Ozone.
(e) Other damaging substances and conditions.
(9) Protector gloves shall be worn over insulating gloves, except under the following
conditions:
(a) Protector gloves need not be used with class 0 gloves, under limited-use
conditions, when small equipment and parts manipulation necessitate unusually high
finger dexterity.
Note to subrule (9)(a): Persons inspecting rubber insulating gloves used under these
conditions shall take extra care in visually examining them. Employees using rubber
insulating gloves under these conditions shall take extra care to avoid handling sharp
objects.
(b) If the voltage does not exceed 250 volts, ac, or 375 volts, direct current, protector
gloves shall not be used with class 00 gloves, under limited-use conditions, when small
equipment and parts manipulation necessitate unusually high finger dexterity.
Note to subrule (9)(b): Persons inspecting rubber insulating gloves used under these
conditions shall take extra care in visually examining them. Employees using rubber
insulating gloves under these conditions shall take extra care to avoid handling sharp
objects.
(c) Any other class of glove may be used without protector gloves, under limited-use
conditions, when small equipment and parts manipulation necessitate unusually high
finger dexterity but only if the employer can demonstrate that the possibility of physical
damage to the gloves is small and if the class of glove is 1 class higher than that required
for the voltage involved.
(d) Insulating gloves that have been used without protector gloves may not be reused
until they have been tested under the provisions of this rule.
(10) Electrical protective equipment shall be subjected to periodic electrical tests.
Test voltages and the maximum intervals between tests shall be pursuant to Table D and
Table E.
(11) The test method used in this rule shall reliably indicate whether the insulating
equipment can withstand the voltages involved.
Note to subrule (11): The standard electrical test methods considered as meeting this
requirement are listed in Table 3.
(12) Insulating equipment failing to pass inspections or electrical tests shall not be
used by employees, except as follows:
(a) Rubber insulating line hose may be used in shorter lengths with the defective
portion cut off.
(b) Rubber insulating blankets may be salvaged by severing the defective area from
the undamaged portion of the blanket. The resulting undamaged area shall not be smaller
than 560 millimeters by 560 millimeters (22 inches by 22 inches) for class 1, 2, 3, and 4
blankets.
(c) Rubber insulating blankets shall be repaired using a compatible patch that results
in physical and electrical properties equal to those of the blanket.
(d) Rubber insulating gloves and sleeves with minor physical defects, such as small
cuts, tears, or punctures, shall be repaired by the application of a compatible patch. Also,
rubber insulating gloves and sleeves with minor surface blemishes shall be repaired with
a compatible liquid compound. The repaired area shall have electrical and physical
properties equal to those of the surrounding material. Repairs to gloves shall be permitted
only in the area between the wrist and the reinforced edge of the opening.
(13) An employer shall ensure that repaired insulating equipment is retested before it
is used by employees.
(14) The employer shall certify that equipment has been tested pursuant to the
requirements of this rule. The certification shall identify the equipment that passed the
test and the date it was tested and shall be made available upon request to the department
of licensing and regulatory affairs director and to MIOSHA employees or their authorized
representatives.
Note to subrule (14): Marking equipment with, and entering onto logs, the results of
the tests and the dates of testing are acceptable means of meeting the certification
requirement.
TABLE 3
AMERICAN SOCIETY OF TESTING MATERIALS STANDARDS
STANDARD TITLE
ASTM
NUMBER
EDITIO
N
SUPPLEM
ENT
Standard Specification for Rubber
Insulating Gloves
D-120
2009
-
Standard Specification for Rubber
Insulating Matting
D-178
2001
2010
Standard Specification for Rubber
Insulating Blankets
D-1048
2012
Standard Specification for Rubber
Insulating Covers
D-1049
1998
2010
Standard Specification for Rubber
Insulating Line Hose
D-1050
2005
2011
Standard Specification for Rubber
Insulating Sleeves
D-1051
2008
-
Standard Specification for
In-Service Care of Insulating
Line Hose and Covers
F-478
2009
-
Standard
Specification
for
In-Service Care of Insulating Blankets
F-479
2006
2011
Standard
Specification
for
In-Service Care of Insulating Gloves
And Sleeves
F-496
2008
-
TABLE A
ALTERNATING CURRENT PROOF-TEST REQUIREMENTS
CLASS OF
EQUIPMENT
PROOF-TE
ST
VOLTAGE
RMS V
Maximum Proof-Test Current, mA
(Globes Only)
280-m
m
(11
in.)
Glove
360-m
m
(14
in.) Glove
410-m
m
(16
in.) Glove
460-m
m
(18
in.) Glove
00
2,500
8
12
-
-
0
5,000
8
12
14
16
1
10,000
-
14
16
18
2
20,000
-
16
18
20
3
30,000
-
18
20
22
4
40,000
-
-
22
24
TABLE B
DIRECT CURRENT PROOF-TEST REQUIREMENTS
CLASS OF EQUIPMENT
PROOF-TEST VOLTAGE
00
10,000
0
20,000
1
40,000
2
50,000
3
60,000
4
70,000
NOTE: The dc voltages listed in this table are not appropriate for proof testing
rubber insulating line hose or covers. For this equipment, dc proof tests shall use a
voltage high enough to indicate that the equipment can be safely used at the voltages
listed in Table D.
See ASTM D-1050 “Standard Specification for Rubber Insulating Line Hose,”
2005 edition with 2011 supplement and ASTM D-1049 “Standard Specification for
Rubber Insulating Covers,” 1998 edition with 2010 supplement, as adopted in
R 408.13301a, for further information on proof tests for rubber insulating line hose and
covers, respectively.
TABLE C
GLOVE TESTS – WATER LEVEL1, 2
CLASS OF
GLOVE
ALTERNATING
CURRENT
PROOF TEST
DIRECT CURRENT
PROOF TEST
mm
in
mm
in
00
38
1.5
38
1.5
0
38
1.5
38
1.5
1
38
1.5
51
2.0
2
64
2.5
76
3.0
3
89
3.5
102
4.0
4
127
5.0
153
6.0
1 The water level is given as the clearance from the reinforced edge of the glove to
the water line, with a tolerance of ±13 mm. (±0.5 in.).
2 If atmospheric conditions make the specified clearances impractical, the
clearances may be increased by a maximum of 25 mm. (1 in.).
TABLE D
RUBBER INSULATING EQUIPMENT, VOLTAGE REQUIREMENTS
CLASS
OF
EQUIPMENT
MAXIMUM
USE VOLTAGE1
ALTERNATIN
G CURRENT RMS
RETEST
VOLTAGE2
ALTERNATIN
G CURRENT RMS
RETEST
VOLTAGE2
DIRECT
CURRENT AVG
00
500
2,500
10,000
0
1,000
5,000
20,000
1
7,500
10,000
40,000
2
17,000
20,000
50,000
3
26,500
30,000
60,000
4
36,000
40,000
70,000
1 The maximum use voltage is the ac voltage (rms) classification of the protective
equipment that designates the maximum nominal design voltage of the energized
system that may be safely worked. The nominal design voltage is equal to the
phase-to-phase voltage on multiphase circuits. However, the phase-to-ground potential
is considered to be the nominal design voltage under the following conditions:
(1) There is no multiphase exposure in a system area and the voltage exposure is
limited to the phase-to-ground potential, or
(2) The electric equipment and devices are insulated or isolated or both so that the
multiphase exposure on a grounded wye circuit is removed.
2 The proof-test voltage shall be applied continuously for at least 1 minute, but no
more than 3 minutes.
TABLE E
RUBBER INSULATING EQUIPMENT TEST INTERVALS
TYPE
OF
EQUIPMENT
WHEN TO TEST
Rubber insulating line
hose
Upon indication that insulating value
is suspect and after repair.
Rubber
insulating
covers
Upon indication that insulating value
is suspect and after repair.
Rubber
insulating
blankets
Before first issue and every 12 months thereafter;1
upon indication that insulating value is suspect;
and after repair
Rubber
insulating
gloves
Before first issue and every 6 months thereafter;1
upon indication that insulating value is suspect;
after repair; and after use without protectors
Rubber
insulating
sleeves
Before first issue and every 12 months thereafter;1
upon indication that insulating value is suspect;
and after repair
1 If the insulating equipment has been electrically tested but not issued for service,
the insulating equipment shall not be placed into service unless it has been electrically
tested within the previous 12 months.