R 408.13847
R 408.13847 Hot sticks.
Cite as Mich. Admin. Code R 408.13847
Rule 3847. (1) A hot stick and any tool attached to it shall be clean and inspected for
damage before use.
(2) A hot stick which has been repaired by a knowledgeable employee or an outside
service and tested to meet the requirements of subrule (3) of this rule.
(3) A new hot stick purchased after June 1, 1983, shall not be used unless it has been
certified and labeled by the manufacturer to meet the following standards:
(a) Fiberglass, 100,000 volts per foot of length for 5 minutes, or any equivalent test.
(b) Wood, 75,000 volts per foot of length for 3 minutes, or any equivalent test.
(4) A hot stick shall be stored in a manner to protect it from damage. A hot stick made
of wood shall be protected from moisture.
(5) A hot stick shall not be used in excess of the rated capacity certified by the
manufacturer.
(6) The minimum working distance and minimum clear hot stick distances prescribed in
table 1, when using live-line tools, shall not be violated.
(7) Table 1 reads as follows:
TABLE 1
ALTERNATING CURRENT — MINIMUM DISTANCES
Voltage Range
(Phase To Phase) Kilovolt
Minimum Working and Clear Hot Stick
Distance
2.1 to 15
2 ft. 0 in.
15.1 to 35
2 ft. 4 in.
35.1 to 46
2 ft. 6 in.
46.1 to 72.5
3 ft. 0 in.
72.6 to 121
3 ft. 4 in.
138 to 145
3 ft. 6 in.
161 to 169
3 ft. 8 in.
230 to 242
5 ft. 0 in.
345 to 362
17 ft. 0 in.
500 to 552
111 ft. 0 in
700 to 765
115 ft. 0 in.
1NOTE: For 345-362 kV. 500-552 kV. and 700-765 kV., the minimum working distance
and the minimum clear hot stick distance may be reduced provided that such distances
are not less than the shortest distance between the energized part and the grounded
surface.
PORTABLE POWERED TOOL PROVISIONS