R 408.14495
R 408.14495 Chlorine, caustic and acid.
Cite as Mich. Admin. Code R 408.14495
Rule 4495. (1) Liquid chlorine shall be stored in an unoccupied ventilated
room. The exhaust pickup shall be at floor level.
(2) A room used for storage of chlorine gas shall have not less than 2 exits.
(3) A tank car containing chlorine and connected to a pipe or hose line shall be
protected by a derail device and a blue flag.
(4) A pipe or hose line carrying chlorine, caustic oR acid shall be identified by a
sign or color label.
(5) Where chlorine is piped through a wall, shut-off valves shall be located on
both sides of the wall and at the inlet and outlet.