R 408.15321
R 408.15321 Electrical hazards.
Cite as Mich. Admin. Code R 408.15321
Rule 5321. (1) An electric conductor or communication line shall be considered
energized unless the systems utility or owner indicates otherwise and they have
visibly grounded the conductor or line.
(2) The location of underground utilities shall be determined before any digging or
ditching operations are started.
(3) A tree worker or qualified line clearance tree trimmer shall not make a direct
contact with an energized conductor.
(4) A tree worker shall maintain his body and tools not less than the distance
prescribed in table 1 from an energized conductor. If these clearances cannot be
maintained, the systems operator or owner shall be contacted to deenergize the
conductor or provide protective measures or devices before the work is started.
(5) A qualified line clearance tree trimmer shall maintain his body and tools not
less than the distance prescribed in table 2 from an energized conductor, except the
trimmer may remove branches hanging on a conductor using approved insulated tools
and equipment when the voltage is below 10 kv.
(6) A branch hanging on a conductor energized at more than 10 kv shall be
removed after the line is deenergized or removed by an authorized and trained
systems operator employee or owner employee using approved protective tools and
equipment.
TABLE 1
Minimum Working Distances for Tree Workers
Voltage
Minimum Distance
0 to 300 volts 1 foot (.305 M)
301 to 750 volts 2 feet (.610 M)
751 to 50 kv 10 feet (3.05 M)
50 kv or more .4 inch per 100 volts
TABLE 2
Minimum Working Distances for
Qualified Line Clearance Tree Trimmers
Voltage Range
Minimum Working
(phase to phase)
Distance
O to 750 v
1 ft. ( .305 M)
751 to 35 kv
2 ft. 4 in. ( .711 M)
35.1 kv to 46.0 kv
2 ft. 6 in. ( .762 M)
46.1 kv to 72.5 kv
3 ft. 0 in. ( .914 M)
72.6 kv to 121.0 kv
3 ft. 4 in. (1.016 M)
138.0 kv to 145.0 kv 3 ft. 6 in. (1.067 M)
161.0 kv to 169.0 kv 3 ft. 8 in. (1.118 M)
230.0 kv to 242.0 kv 5 ft. 0 in. (1.524 M)
345.0 kv to 362.0 kv 7 ft. 0 in. (2.134 M)
500.0 kv to 552.0 kv 11 ft. 0 in. (3.453 M)
700.0 kv to 765.0 kv 15 ft. 0 in. (4.572 M)
WORK PRACTICES