R 408.17225

R 408.17225 Flammables, painting and coating

Last amended: 2013Year: 2026Length: 133 wordsOfficial source

Cite as Mich. Admin. Code R 408.17225

Rule 7225. (1) A Class I flammable solvent stored inside a building shall be in an approved safety can with an automatic closing cap and flame arrestor or original unopened container having a capacity of not more than 5 gallons. Quantities in excess of 5 gallons shall be stored as prescribed by flammable liquid regulations of the fire marshal promulgated under 1941 PA 207. (2) When pouring a flammable solvent from 1 container to another, continuous contact between the containers shall be maintained or a bonding or grounding strap shall connect the containers. (3) A Class I flammable solvent shall not be used for cleaning tools, parts, floors, or booths. (4) When a flammable liquid is removed from a vehicle tank, an approved pumping device equipped with a ground strap shall be used.