R 408.17225
R 408.17225 Flammables, painting and coating
Cite as Mich. Admin. Code R 408.17225
Rule 7225. (1) A Class I flammable solvent stored inside a building shall be in an
approved safety can with an automatic closing cap and flame arrestor or original
unopened container having a capacity of not more than 5 gallons. Quantities in excess of
5 gallons shall be stored as prescribed by flammable liquid regulations of the fire marshal
promulgated under 1941 PA 207.
(2) When pouring a flammable solvent from 1 container to another, continuous
contact between the containers shall be maintained or a bonding or grounding strap shall
connect the containers.
(3) A Class I flammable solvent shall not be used for cleaning tools, parts, floors, or
booths.
(4) When a flammable liquid is removed from a vehicle tank, an approved pumping
device equipped with a ground strap shall be used.