R 408.40722 Storage.
Cite as Mich. Admin. Code R 408.40722
Rule 722. (1) An oxygen cylinder shall be stored not less than 20 feet from fuel gas
cylinders or any highly combustible material, such as, but not limited to, oil, grease,
excelsior, flammable gas, or a source of ignition, or shall be separated from the material
by a noncombustible wall not less than 5 feet (1.6 meters) high which has a fire resistance
rating of 30 minutes.
(2) A cylinder shall be stored away from any source of heat more than 125 degrees
Fahrenheit.
(3) A cylinder, whether full or empty, in storage or during shipment, or with the
regulator removed, shall have the valve closed and the cap connected in place if a cap is
provided in the design, or shall be otherwise protected.
(4) Where different gases are stored, they shall be grouped by types. Groupings shall
separate the fuel gases from the oxidizing gases as specified in subrule (1) of this rule.
(5) A storage area for cylinders shall be well ventilated.
(6) A cylinder shall not be stored in basements or pits.
(7) Where a liquid or gaseous oxygen system is used to supply gaseous oxygen for
welding and cutting and the system has a storage capacity of more than 20,000 cubic feet
(560 cubic meters), measured at 14.7 psia and 70 degrees Fahrenheit, including
unconnected reserves at the site, the system shall be as prescribed in National Fire
Protection Association Standard NFPA 50, “Standards for Bulk Oxygen Systems at
Consumer Sites,” 1974 edition, which is adopted by reference in R 408.40709.