R 408.40744 Installation.
Cite as Mich. Admin. Code R 408.40744
Rule 744. (1) The frame or case of a welding machine shall be grounded, unless the
manufacturer does not recommend it.
(2) The work on which the operator welds shall be grounded. A wire used to ground
a workpiece shall be capable of carrying the full welding current. Connections of the
ground shall be mechanically sound and strong. When a single ground return cable
services more than 1 unit, the safe current-carrying capacity of the cable shall equal or
exceed the total maximum output capacities of all units which it services.
(3) A conduit containing an electrical conductor shall not be used for completing a
work-lead circuit.
(4) A pipeline in service shall not be used as a permanent part of a work-lead circuit,
but may be used during construction, extension, or repair if current is not carried through
threaded joints, flanged bolted joints, or caulked joints and if special precautions are used
to avoid sparking at the connection of the work-lead cable.
(5) Chains, wire ropes, cranes, hoists, and elevators used for carrying loads shall not
be used to carry a welding current.
(6) A welding cable shall be protected against damage, entanglement, or contact with
power supply or high-tension wires.
(7) A welding machine that is not provided with a controller or disconnect switch as
an integral part shall have a controller or disconnect switch with overload protection
provided. A disconnect switch with overload protection or overload disconnect
protection, or equivalent, shall be provided for each outlet used by a portable welding
machine, unless the machine is equipped with a disconnect switch and overload
protection.
(8) The rated current-carrying capacity of the supply conductors for individual
machines shall not be less than the rated primary current for the welding machine. The
rated current-carrying capacity of the conductors for a group of welding machines may be
less than the sum of the rated primary current of the welding machines supplied. The
conductor rating shall be determined in each case according to the machine loading based
on the use to be made of each welding machine and the allowance permissible if all the
machines supplied by the conductor will not be in use at the same time.
(9) Where a welding machine is working sufficiently close to another machine so that
a welding operator is likely to touch the exposed parts of more than 1 electrode holder
simultaneously, the machine shall be connected so as to minimize shock hazard as
follows:
(a) DC machine shall be connected with the same polarity.
(b) AC machine shall be connected to the same phase of the supply circuit and with
the same instantaneous polarity.
(10) A current-carrying part passing through the portion of the holder that the
employee grips by hand and the outer surface of the jaws of the holder shall be insulated
against the maximum voltage encountered to ground.