R 408.41212 Accumulation of tools, material, or debris prohibited; weather conditions; slippery conditions; electrical hazards; rope protection; fall protection.
Cite as Mich. Admin. Code R 408.41212
Rule 1212. (1) Excess tools, materials, and debris shall not be permitted to
accumulate on a scaffold to create a hazard.
(2) Work on or from scaffolds is prohibited during storms or high winds unless a
competent person has determined that it is safe for employees to be on a scaffold and that
the employees are protected by a personal fall arrest system. Wind screens shall not be
used unless the scaffold is secured against the anticipated wind forces imposed.
(3) A scaffold shall be kept free of slippery conditions such as those caused by ice,
snow, oil, grease, or other slippery compounds.
(4) An employee shall not be allowed within 10 feet of uninsulated electrical
energized lines.
(5) Before a scaffold is erected within 10 feet of a power line all of the following
requirements shall be met, as applicable:
(a) The utility or property owner is consulted.
(b) A power line or electrical apparatus is considered energized unless the property
owner or utility indicates it is de-energized and the line or apparatus is visibly grounded.
If de-energizing is impractical and the equipment is exposed to contact by an employee,
the minimum clearances in table 1 shall be maintained between the scaffold, employee,
or material, whichever is closer.
(c) The requirements for employees performing power transmission and distribution
work, electrical work, or telecommunications work are found in Construction Safety
Standard Part 16. “Power Transmission and Distribution,” Construction Safety Standard
Part 17. “Electrical Installations,” and in Construction Safety and Health Standard Part
30. “Telecommunications for Constructions,” as referenced in R 408.41201.
(6) Table 1 reads as follows:
TABLE 1
INSULATED LINES
VOLTAGE
MINIMUM
DISTANCE
ALTERNATIVES
Less than 300 volts
3 feet (0.9 meters)
300
volts
to
50
kilovolts
10 feet (3.1 meters)
More than 50 kilovolts
10 feet (3.1 meters)
plus 0.4 inches
(1.0 centimeter)
for each kilovolt over
50 kilovolts
2 times the length of
the line insulator,
but not less than 10 feet
(3.1 meters)
UNINSULATED LINES
VOLTAGE
MINIMUM
DISTANCE
ALTERNATIVES
Less than 50 kilovolts
10 feet (3.1 meters)
More than 50 kilovolts
10 feet (3.1 meters)
Plus
0.4
inches
(1.0 centimeter)
for each kilovolt over
50 kilovolts
2 times the length of
the line insulator,
but not less than 10 feet
(3.1 meters)
(7) Welding, burning, riveting, or open flame work shall not be performed within 10
feet of fiber or synthetic rope that is used to suspend a scaffold, unless the rope is
protected from sparks, flame, or hot metal. Only treated or protected fiber or synthetic
ropes shall be used for or near any work that involves the use of corrosive substances or
chemicals.
(8) A suspension rope, including connecting hardware, used on nonadjustable or
adjustable suspension scaffolds shall be capable of supporting, without failure, not less
than 6 times the maximum intended load applied or transmitted to the rope.
(9) If personal fall arrest systems are required by these rules for the protection of
employees, then the arrest system equipment shall be as prescribed in Construction
Safety Standard Part 45. “Fall Protection,” as referenced in R 408.41201.
(10) To reduce the possibility of welding current arcing through the suspension wire
rope when performing welding from suspended scaffolds, a welder shall take the
following precautions, as applicable:
(a) An insulated thimble shall be used to attach each suspension wire rope to its
hanging support, such as a cornice hook or outrigger. Excess suspension wire rope and
any additional independent lines from grounding shall be insulated.
(b) The suspension wire rope shall be covered with insulating material extending not
less than 4 feet (1.2 meters) above the hoist. If there is a tail line below the hoist, it shall
be insulated to prevent contact with the platform. The position of the tail line that hangs
free below the scaffold shall be guided or retained, or both, so that it does not become
grounded.
(c) Each hoist shall be covered with insulated protective covers.
(d) In addition to a work lead attachment required by the welding process, a
grounding conductor shall be connected from the scaffold to the structure. The size of the
conductor shall be at least the size of the welding process work lead, and the conductor
shall not be in series with the welding process or the workpiece.
(e) If the scaffold grounding lead is disconnected, the welding machine shall be shut
off.
(f) An active welding rod or uninsulated welding lead shall not be allowed to contact
the scaffold or its suspension system.