R 408.41515
R 408.41515 Power line clearances; generally.
Cite as Mich. Admin. Code R 408.41515
Rule 1515. (1) When working in proximity to power lines, all equipment covered by this part
shall maintain clearances as prescribed in Table A “Minimum Clearance Distances.”
(2) When traveling with no load in proximity to power lines, all equipment covered by this
part shall maintain clearances as prescribed in Table B “Minimum Clearance Distances While
Traveling with No Load.”
(3) The employer shall designate an employee to observe the clearance and give timely
warning if it is difficult for the operator to maintain the prescribed clearance by visual means.
TABLE A
MINIMUM CLEARANCE DISTANCES
Voltage
(nominal, kV, alternating current)
Minimum clearance distance (feet)
up to 50
10
over 50 to 200
15
over 200 to 350
20
over 350 to 500
25
over 500 to 750
35
over 750 to 1,000
45
over 1,000
(as established by the utility owner or
operator
or
registered
professional
engineer who is a qualified person with
respect to electrical power transmission
and distribution)
Note: The value that follows ‘‘to’’ is up to and includes that value.
For example, over 50 to 200 means up to and including 200kV.
TABLE B
MINIMUM CLEARANCE DISTANCES WHILE TRAVELING WITH NO LOAD
Voltage
(nominal, kV, alternating current)
Minimum clearance distance (feet)
while traveling
Up to 0.75
4
Over .75 to 50
6
Over 50 to 345
10
Over 345 to 750
16
Over 750 to 1,000
20
Over 1,000
(as established by the utility owner or
operator
or
registered
professional
engineer who is a qualified person with
respect to electrical power transmission
and distribution)
EXCAVATORS