R 408.41728 Grounding and bonding.
Cite as Mich. Admin. Code R 408.41728
Rule 1728. (1) A grounding circuit shall be continuous, be capable of carrying the
current imposed on it, and have a resistance low enough to permit sufficient current to
flow to cause the fuse or circuit breaker to interrupt the current.
(2) Non-electrical equipment. The metal parts of the following non-electrical equipment
shall be grounded:
(a) Frames and tracks of electrically operated cranes.
(b) Frames of non-electrically driven elevator cars to which electric conductors are
attached.
(c) Hand-operated metal shifting ropes or cables of electric elevators.
(d) Metal partitions, grill work, and similar metal enclosures around equipment of
over 1 kV between conductors.
(3) Driven rod electrodes, either singly or connected, shall have a resistance to ground
of not more than 25 ohms.
(4) Conductors used for bonding shall be capable of carrying the imposed current. The
bonding clamps shall have a secure and positive metal-to-metal contact.