R 408.41851
R 408.41851 Portable fire extinguishing equipment; selection and installation.
Cite as Mich. Admin. Code R 408.41851
Rule 1851. (1) All portable fire extinguishers shall bear an approved label of a
nationally recognized testing laboratory.
A fire extinguisher or extinguishing device that contains an active agent or propellant
that has thermal decomposition products that have a level of vapor toxicity equal to or
greater than any of the following listed materials shall not be used, installed for use, or
allowed to remain installed for use:
(a) Carbon tetrachloride, CCL4.
(b) Chlorobromomethane, CH2 BrCL.
(c) Azeotropic chlormethane, CM7.
(d) Dibromodifluoromethane, CBr2F2.
(e) 1, 2-dibromo-2-chloro-1, 1, 2-trifluoroethane, Cbr-F2, CBrCLf.
(f) 1, 2-dibromo-2, 2-difluoroethane, CH2BrCbrF2.
(g) Methylbromide, CH3Br.
(h) Ethylene dibromide, CH2BrCH2Br.
(i) Hydrogen bromide, HBr.
(j) Methylene bromide, CH2Br2.
(k) Bromodifluoromethane, CHBrF2.
(2) A fire extinguisher, rated not less than 2A, shall be provided for each 3,000
square feet of the protected building area, or major fraction thereof. Travel distance from
any point of the protected area to the nearest fire extinguisher shall not exceed 100 feet.
(3) One or more fire extinguishers, rated not less than 2A, shall be provided on each
floor. In multistory buildings, at least 1 fire extinguisher shall be located adjacent to
stairway.
(4) Fire fighting equipment shall be located where it will be readily seen and
accessible along normal paths of travel in the protected area.
(5) One 55-gallon open drum of water and 2 fire pails may be substituted for a fire
extinguisher that has a 2A rating. Extinguishers and water drums, subject to freezing,
shall be protected from freezing.
(6) A 1/2 inch or larger interior diameter garden hose that is not more than 100 feet
in length and that is equipped with a nozzle may be substituted for a 2A fire extinguisher
if it is capable of reaching all points in the area that would be covered by the replaced
extinguisher and is capable of discharging not less than 5 gallons per minute with a
horizontal hose stream of not less than 30 feet. The hose line shall be mounted on a rack
or reel. Not more than 1/2 of the total number of required fire extinguishers may be
replaced by the hose.
(7) In addition to the requirements of this rule, fire extinguishers shall be supplied as
follows:
(a) Not less than 1 portable fire extinguisher that has a rating of not less than 20 BC
units shall be located as follows:
(i) Outside of, but not more than 10 feet from, a door opening to a room used for the
storage of more than 60 gallons of flammable liquids.
(ii) Not less than 25 feet, nor more than 75 feet, from an outside storage area.
(iii) On each tank truck or other vehicle used to transport or dispense flammable
liquids.
(iv) A fire extinguisher, rated not less than 10B, shall be provided within 50 feet of
wherever more than 5 gallons of flammable or combustible liquids or 5 pounds of
flammable gas are being used on the jobsite. This requirement does not apply to the
integral fuel tanks of motor vehicles.
(b) Each service or fueling area shall have at least 1 portable fire extinguisher which
has not less than a 20 BC unit rating and which is located within 75 feet of each pump,
dispenser, underground fill opening, and lubricating or service area.
(c) Storage locations for liquefied petroleum gas (L.P.G.) shall be provided with at
least 1 approved portable fire extinguisher that has a rating of not less than 20 BC.
(d) Each site of a hazardous process shall be provided with a portable fire
extinguisher of an appropriate size and type. Other means for safety or control may be
provided if approved or required by the process.
(8) Table 1 may be used in selecting and providing an extinguisher.
(9) Table 1 reads as follows:
TABLE 1
HAZARD
DESCRIPTI
ON
EXTINGUISHER
TYPE
AND
CONTENTS
Class
"A"
Fire
Combustible
Material
Loaded
stream,
Multipurpose
dry
chemical, Pressure-operated water, Water
pump tanks, Water mist, Halon 1211.
Class
"B"
Fire
Flammable
Liquids, Gas,
Or Grease
Carbon dioxide, Dry chemical, Foam,
Loaded
stream,
Multipurpose
dry
chemical, Halon 1211.
Class
"C"
Fire
Electrical
Equipment
Carbon dioxide with plastic horn only,
Dry chemical, Multipurpose dry chemical,
Water mist, Halon 1211.
Class
"D"
Fire
Combustible
Metal
Extinguishing agent listed for use on a
specific combustible metal hazard.