R 408.41853
R 408.41853 Fixed fire equipment.
Cite as Mich. Admin. Code R 408.41853
Rule 1853. (1) Sprinkler protection shall be as follows:
(a) If the facility being constructed includes the installation of automatic sprinkler
protection, the installation shall closely follow the construction and be placed in service
as soon as applicable laws permit following completion of each story.
(b) In all structures in which standpipes are required, or where standpipes exist in
structures being altered, they shall be brought up as soon as applicable laws permit, and
shall be maintained as construction progresses in such a manner that they are always
ready for fire protection use. The standpipes shall be provided with Siamese fire
department connections on the outside of the structure, at the street level, which shall be
conspicuously marked.
(2) During demolition or alterations, an existing sprinkler or standpipe system shall
be maintained in service in any portion of a structure that is not subject to demolition or
alteration. The operation of a sprinkler control valve shall be permitted only by a properly
authorized person. Modification of a sprinkler system to permit alterations or additional
demolition shall be expedited so that the automatic protection may be returned to service
as quickly as possible. Sprinkler control valves shall be checked daily at the close of
work to ascertain whether the protection is in service. When the sprinkler or standpipe
system is out of service for other than routine maintenance, the local fire department and
the building manager or designated representative shall be notified. A sign shall be posted
on each fire department connection that is out of service and the balance of the service
shall be tested and resealed in operable condition, where required, and both the fire
department and the building manager or designated representative shall be advised that
the system is again in service.
(3) A standpipe and hose system shall have not less than 1 outlet per story.
(4) An automatic sprinkler system shall be installed and maintained as prescribed in
The National Fire Protection Association Standards NFPA 13 "Installation of Sprinkler
Systems," 1991 edition; NFPA 14 "Standard For The Installation Of Standpipe, Private
Hydrants And Hose Systems," 2000 edition; and NFPA 25 "Inspection, Testing, And
Maintenance Of Water-Based Fire Protection Systems," 1998 edition. The standards are
adopted by reference in R 408.41802.