R 408.41855
R 408.41855 Fire hose and connections.
Cite as Mich. Admin. Code R 408.41855
Rule 1855. (1) One-hundred feet or less of 1-1/2 inch hose, with a nozzle capable of
discharging water at 25 gallons or more per minute supplied from an approved standpipe
system may be substituted for a fire extinguisher rated not more than 2A in the
designated area provided that the hose line can reach all points in the area.
(2) The employer shall contact the local fire fighting organization to assure that fire
hose connections on the jobsite are compatible with their fire fighting equipment. If a
connection is not compatible, the employer shall install an adapter, or equivalent, to
permit connection of local fire fighting equipment.
(3) During demolition involving combustible materials, charged hose lines, supplied
by hydrants, water tank trucks with pumps, or equivalent, shall be made available.