R 408.41865
R 408.41865 Outside storage.
Cite as Mich. Admin. Code R 408.41865
Rule 1865. (1) Containers of flammable liquids with not more than 60 gallons in
each container shall not be stored in excess of 1,100 gallons in any outside storage area.
(2) Portable tanks stored outside shall not be closer than 20 feet from any building.
Two or more portable tanks, grouped together, having a combined capacity in excess of
2,200 gallons, shall be separated by a 5-foot clear area. Individual portable tanks
exceeding 1,100 gallons shall be separated by a 5-foot clear area. Piles or groups of
containers shall be separated by a 5-foot clearance.
(3) Within 200 feet of each portable tank, there shall be a 12-foot wide access way
to permit approach of fire control apparatus.
(4) A flammable liquid in an outdoor storage area shall be stored not less than 20
feet from a building.
(5) Within 200 feet of each pile or group of flammable containers, a 12-foot wide
access way shall be maintained to permit the approach of fire control equipment.
(6) An outside storage area for flammable liquids shall be graded in a manner to
divert a possible spill away from a building or other hazard, or shall be surrounded by a
curb or earth dike not less than 12 inches high.
When a curb or dike is used, provisions shall be made to drain off accumulations of
water or a spill of a flammable liquid in such a manner that the spill cannot create a
hazard for an employee.
The drains shall terminate in a location that will not create another hazard.
(7) An outside storage area for flammable liquid shall be kept free of weeds, papers,
debris, and other combustibles not necessary to the storage.
(8) An above ground tank or loading operation shall not be installed closer than 25
feet plus 1 inch per 1,000 volts, measured horizontally, from the center line of electric
power lines, or under an electric power line, except that service entrance and service lines
may be closer than 25 feet but not over the tanks or loading area. This prohibition shall
not apply to a fuel oil tank with up to a 275-gallon individual capacity or a 550-gallon
aggregate capacity that is used for heating purposes.
(9) A flammable or combustible liquid outdoor storage area shall not occupy any
area used as a means of egress.
(10) Underground tanks shall not be abandoned.