R 408.41877a
R 408.41877a Systems utilizing containers other than DOT containers.
Cite as Mich. Admin. Code R 408.41877a
Rule 1877a. (1) This rule applies specifically to systems utilizing storage containers
other than those constructed in accordance with DOT specifications. R 408.41875(4)
applies to this rule unless otherwise noted in R 408.41875(4).
(2) Storage containers shall be designed and classified in accordance with Table 5.
TABLE 5
Contai
ner
Type
For gases with vapor
press.
Not to exceed lb.
MINIMUM
DESIGN
PRESSURE
OF
CONTAINER,
LB. PER SQ. IN. GAGE
per sq. in.
gage at 100 deg. F.
(37.8 deg. C.)
1949
and
earlier
editions
of ASME Code
(Par. U-68, U-69)
1949
edition
of
ASME Code (Par. U-200,
U-201);
1950,
1952,
1956,
1959, 1962, 1965, and
1968
(Division
1)
editions of ASME Code;
All editions of
API-ASME Code(3)
80(1)
80(1)
80 (1)
100 (1)
100
100
100
125
125
125
125
156
150
150
150
187
175
175
175
219
200(2)
215
200
250
Footnote(1) New storage containers of the 80 type have not been authorized since Dec. 31,
1947.
Footnote(2) Container type may be increased by increments of 25.
The minimum design pressure of containers shall per 100 percent of the container type
designation when constructed under 1949 or earlier editions of the ASME Code (Par. U-68 and
U-69).
The minimum design pressure of containers shall be 125 percent of the container type
designation when constructed under: (1) the 1949 ASME Code (Par. U-200 and U-201), (2)
1950, 1952, 1956, 1959, 1962, 1965, and 1968 (Division 1) editions of the ASME Code, and
(3) all editions of the API-ASME Code.
Footnote(3) Construction of containers under the API-ASME Code is not authorized after
July 1, 1961.
(3) Containers with foundations attached, portable or semiportable b containers with
suitable steel "runners" or "skids" and popularly known in the industry as "skid tanks,"
shall be designed, installed, and used in accordance with these rules subject to the
following provisions:
(a) If they are to be used at a given general location for a temporary period not to
exceed 6 months they need not have fire-resisting foundations or saddles but shall have
adequate ferrous metal supports.
(b) They shall not be located with the outside bottom of the container shell more
than 5 feet, 1.52 m, above the surface of the ground unless fire-resisting supports are
provided.
(c) The bottom of the skids shall not be less than 2 inches, 5.08 cm, or more than 12
inches, 30.48 cm, below the outside bottom of the container shell.
(d) Flanges, nozzles, valves, fittings, and the like, having communication with the
interior of the container, shall be protected against physical damage.
(e) When not permanently located on fire-resisting foundations, piping connections
shall be sufficiently flexible to minimize the possibility of breakage or leakage of
connections if the container settles, moves, or is otherwise displaced.
(f) Skids, or lugs for attachment of skids, shall be secured to the container in
accordance with the code or rules under which the container is designed and built, with a
minimum factor of safety of 4, to withstand loading in any direction equal to 4 times the
weight of the container and attachments when filled to the maximum permissible loaded
weight.
(4) Field welding where necessary shall be made only on saddle plates or brackets
that were applied by the manufacturer of the tank.