R 408.41980
R 408.41980 Air receivers.
Cite as Mich. Admin. Code R 408.41980
Rule 1980. (1) All new air receivers installed after July 28, 1995, shall be
constructed in accordance with the American Society Of Mechanical Engineers (ASME)
“Boiler And Pressure Vessel Code,” Section VIII, “Unfired Pressure Vessels,” 1980
edition which is adopted by reference in R 408.41902.
(2) All safety valves used shall be constructed, installed, and maintained in
accordance with the ASME “Boiler and Pressure Vessel Code,’ Section VIII, “Unfired
Pressure Vessels,” 1980 edition, as adopted in R 408.41902.
(3) Air receivers shall be installed so that all drains, handholes, and manholes are
easily accessible. An air receiver shall not be buried underground or located in an
inaccessible place.
(4) A drain pipe and valve shall be installed at the lowest point of every air receiver
to provide for the removal of accumulated oil and water. Adequate automatic traps may
be installed in addition to drain valves. The drain valve on the air receiver shall be
opened and the receiver completely drained frequently to prevent the accumulation of
excessive amounts of liquid in the receiver.
(5) Every air receiver shall be equipped with an indicating pressure gauge that is
located so that it is readily visible and equipped with 1 or more spring-loaded safety
valves. The total relieving capacity of the safety valves shall be adequate to prevent
pressure in the receiver from exceeding the maximum allowable working pressure of the
receiver by more than 10%.
(6) A valve shall not be placed between the air receiver and its safety valve or
valves.
(7) Safety appliances, such as safety valves, indicating devices, and controlling
devices, shall be constructed, located, and installed so that they cannot be readily
rendered inoperative by any means, including the elements.
(8) All safety valves shall be tested frequently at regular intervals to determine
whether they are in good operating condition.