Rule 2532. (1) Lifting inserts which are embedded or otherwise attached to tilt-up
precast concrete members shall be capable of supporting at least 2 times the maximum
intended load applied or transmitted to them. Lifting inserts which are embedded or
otherwise attached to precast concrete members, other than the tilt-up members, shall be
capable of supporting at least 4 times the maximum intended load applied or transmitted
to them. Lifting hardware shall be capable of supporting at least 5 times the maximum
intended load applied transmitted to the lifting hardware.
(2) An erection and procedure plan, including placement of connections, shall be
prepared by a qualified employee knowledgeable in precast concrete erection and be kept
available at the jobsite.
(3) Precast concrete wall units and vertical panels shall be braced to prevent collapse. A
permanent connection may be used in place of bracing if it is capable of withstanding all
loads imposed during construction.
(4) An employee, except for a connector, shall not be permitted under a precast section,
wall, or panel during lifting and tilting operations.