R 408.43209
R 408.43209 Electrical hazards.
Cite as Mich. Admin. Code R 408.43209
Rule 3209. (1) The employer shall ensure that an aerial work platform shall be
operated so that the distances from energized power lines and equipment prescribed in
Table 1 are maintained, except for the following:
(a) As prescribed in subrule (2) of this rule addressing tree trimming.
(b) As prescribed in subrule (3) of this rule addressing telecommunications.
(c) Where insulating barriers are not a part of or an attachment to the aerial device
that has been erected to prevent physical contact with the lines.
(2) A qualified lineman or a qualified line clearance tree trimmer shall maintain
distances as prescribed in Table 2 when performing work from an aerial work
platform on or near an exposed power line unless any of the following conditions
exist:
(a) The employee is insulated or guarded from the energized part by gloves or
gloves and sleeves, as provided for and prescribed in Construction Safety Standard Part
6. "Personal Protective Equipment" and Construction Safety Standard Part 30.
"Telecommunications."
(b) The employee is insulated, isolated, or guarded from any other conductive
part.
(c) The energized part is insulated from the employee.
(3) A qualified telecommunications employee shall maintain the distances
prescribed in Table 3 when working from an aerial lift, unless the employee is insulated,
isolated, or guarded from any other conductive part or the energized part is insulated
from the employee.
(4) Employees shall use insulated bucket, gloves and sleeves that are rated at
more than the voltage to be worked on or that with which they might come into contact,
to comply with subrules (2) and (3) of this rule.
(5) The clearances, as prescribed in Tables 1-3, do not apply when the owner of
the line or his or her authorized representative, or a utility representative assures that
the conductor is insulated for the system voltages and the task will not compromise
the insulation of the conductor and/or cause an electrical hazard.
(6) Tables 1, 2, and 3 read as follows:
Table
1
Minimum Clearance Distances for Equipment
Voltage
Clearance
With Boom Raised
Clearance
Boom
Lowered
and
No Load in Transit
To 50 kV
10 feet
4 feet
Over 50 kV
10 feet +
.4
inch
per
each 1 kV over 50 kV
10 feet
50 to 345 kV
--
10 feet
346 to 750 kV
--
15 feet
Table
2
Minimum
Working
Distances
for
Qualified Line-Clearance Tree Trimmers and Qualified Linemen
Voltage
Range
Phase to Phase (kilovolts)
Minimum Working Distance
2.1 to 15.0
2 feet 0 inches (61 cm)
15.1 to 35.0
2 feet 4 inches (71 cm)
35.1 to 46.0
2 feet 6 inches (76 cm)
46.1 to 72.5
3 feet 0 inches (91 cm)
72.6 to 121.0
3 feet 4 inches (102 cm)
138.0 to 145.0
3 feet 6 inches (107 cm)
161.0 to 169.0
3 feet 8 inches (112 cm)
230.0 to 242.0
5 feet 0 inches (152 cm)
345.0 to 362.0
*7 feet 0 inches (213 cm)
550.0 to 552.0
*11 feet 0 inches (335 cm
700.0 to 765.0
*15 feet 0 inches (457 cm)
*Note: For 345-362 kV., 500-552 kV., and 700-765 kV., the minimum working distance
and the minimum clear hot stick distance may be reduced that such distances are not
less than the shortest distance between the energized part and a grounded surface.
Table
3
Minimum
Approach
Distances
for
Qualified Telecommunications Employees
Voltage
Range
(Nominal Phase to Phase)
Minimum Approach Distances
300 V and less
1 foot - 0 inches (30.5 cm)
Over 300 V, not over 750 V
1 foot - 6 inches (46 cm)
Over 750 V, not over 2 kV
2 feet - 0 inches (61 cm
Over 2 kV, not over 15 kV
3 feet - 0 inches (91 cm)
Over 15 kV, not over 37 kV
3 feet – 6 inches (107 cm)
Over 37 kV, not over 87.5 kV
4 feet – 0 inches (122 cm)
Over 87.5 kV, not over 121 kV
4 feet – 6 inches (137 cm)
Over 121 kV, not over 140 kV
--