R 299.2487 Incinerators and flares; equipment and design requirements; additional requirements.
Cite as Mich. Admin. Code R 299.2487
Rule 2487. (1) A permittee of a well shall ensure that an incinerator or flare installed
pursuant to R 299.2484(1)(b) or R 299.2486(b) is designed and equipped to prevent the
release of unburned gas to the atmosphere. If the daily volume of gas handled by the
incinerator or flare contains 28 pounds or more of hydrogen sulfide, then a permittee shall
ensure that the incinerator or flare is equipped with a mechanism that operates upon failure
of the pilot light to shut off the flow of fluid from the wellhead.
(2) A permittee of a well subject to this part shall install a fence around an incinerator or
flare as required by R 299.2486(d). A fence shall be located not less than 20 feet from the
base of the incinerator or flare. A permittee of a well shall ensure that warning signs that
have the word "danger" or "caution" followed by the words "poison gas" are posted on all
sides of the fence. If the supervisor of mineral wells or authorized representative of the
supervisor of mineral wells finds that a threat to the public safety still exists due to
emissions of the incinerator or flare, then fencing other than that specified R 299.2302(q)
may be required.
(3) If the supervisor of mineral wells or authorized representative of the supervisor of
mineral wells finds that a threat to the public health or safety exists due to the emission of
sulfur-bearing gasses or vapors, then a flare stack or incinerator stack that is more than 20
feet high, as specified in R 299.2302(s) and R 299.2303(e), may be required.