R 299.9615
R 299.9615 Tank systems.
Cite as Mich. Admin. Code R 299.9615
Rule 615. (1) Owners or operators that use existing or new tank systems, whether
aboveground, in-ground, on-ground, or underground tanks, to treat or store hazardous
waste shall comply with all the requirements of 40 CFR part 264, subpart J, except as
provided in subrule (4) of this rule, and ensure the tank systems are not unfit for use.
(2) Owners or operators of tank systems that do not comply with the containment
requirements of 40 CFR 264.193(b) to (f) shall do all the following until either the tank
system is brought into compliance with the standards of 40 CFR 264.193(a) or until a
variance is obtained as provided by 40 CFR 264.193(h):
(a) Ensure that aboveground tank systems that are used for the treatment or storage of
liquid hazardous wastes, or hazardous wastes that could generate free liquids during
storage, are located in areas which are paved, diked, curbed, or otherwise structurally
enclosed so as to be able to contain not less than 100% of the largest tank system within
the enclosed area. Where the hazardous wastes that are stored are incompatible with the
materials of construction of tank systems within the enclosed area, or where the tank
systems are interconnected so that a loss from one tank system may lead to losses in other
tank systems, the owner or operator shall ensure that all tank systems are structurally
enclosed so as to be able to contain not less than 100% of the liquid portion of the material
being stored in all tank systems.
(b) For underground tank systems that are used for the treatment or storage of liquid
hazardous wastes, or hazardous wastes that could generate free liquids, do all the following:
(i) Provide adequate secondary containment and a leachate collection and withdrawal
system to contain any release of hazardous wastes or hazardous waste constituents from
the tank system.
(ii) Conduct a complete inventory of hazardous wastes in the tank system not less than
twice a month.
(iii) Conduct leachate sampling and analysis not less than once a year. If the inventories
required pursuant to paragraph (ii) of this subdivision indicate a loss of waste, leachate
sampling and analysis be performed within 24 hours of the discovery of the loss.
(3) All tank systems that are put into service after July 14, 1986, or that are upgraded
pursuant to the provisions of 40 CFR 264.193 must be assessed by a corrosion expert in
accordance with the provisions of 40 CFR 264.192(a)(3) and provided with the necessary
corrosion protection as determined pursuant to the assessment.
(4) All tank systems must be designed, constructed, operated, and maintained in
compliance with the requirements of act 207.
(5) Owners or operators shall label tank systems in accordance with the provisions of
NFPA standard no. 704.
(6) The director may waive the interim secondary containment requirements of
subrule (2) of this rule for wastewater treatment units and elementary neutralization units
based upon an assessment of the hydrogeological aspects of the site with respect to the
provisions of part 31, the nature and volume of the waste treated or stored, and the location
and nature of the facility.
(7) NFPA standard no. 704 is adopted by reference in R 299.11002. The provisions of
40 CFR part 264, subpart J, are adopted by reference in R 299.11003. For the purposes of
this adoption, the word "director" replaces the words "regional administrator" and
"administrator" and the words "operating license application" replace the words "part B."