R 323.2236
R 323.2236 Rapid infiltration.
Cite as Mich. Admin. Code R 323.2236
Rule 2236.(1) Rapid infiltration is the application of wastewater to areas of
moderately to highly permeable soil. The majority of applied wastewater percolates
through the soil, and the treated effluent drains naturally to groundwater. The effluent
is minimally treated as it travels through the soil matrix. Vegetation is not typically a
part of the overall treatment process. The utilization of vegetation or its presence
within a discharge area typically does not interfere with system performance. A
facility utilizing rapid infiltration systems for the land treatment of wastewater shall
design
and construct the system under this rule.
(2) The system shall consist of 2 or more cells or absorption areas that can be
alternately loaded and rested or consist of 1 cell or absorption area preceded by an
effluent storage or stabilization pond system. If only 1 cell or absorption area is
provided, then the storage or stabilization pond shall be operated on a fill and draw basis
and have sufficient capacity to allow intermittent loading of the cell or absorption area.
(3) For a system that has more than 1 cell or absorption area, an individual cell
or absorption area of the system shall be capable of being taken out of service without
disrupting application to other cells or absorption areas of the system.
(4) An appropriate hydraulic loading cycle shall be developed and
implemented to maximize long-term infiltration rates and allow for periodic
maintenance.