R 324.1122
R 324.1122 Vessels used for storing hydrogen sulfide-bearing liquid hydrocarbons or hydrogen sulfide-bearing brine; equipment requirements.
Cite as Mich. Admin. Code R 324.1122
Rule 1122. (1) A permittee of a well shall ensure that a vessel which is located at an H2S
well site or in a central production facility serving an H2S well and which is used for the
storage of hydrogen sulfide-bearing liquid hydrocarbons or hydrogen sulfide-bearing brine
is equipped with a sealing, pressure-vacuum-type hatch, except that a pressure-vacuum-
type hatch is not required on a storage vessel if the venting of vapor to the atmosphere is
permitted under subrule (4) of this rule. A hatch shall be kept closed when a tank is not
being gauged.
(2) If a storage vessel described in subrule (1) of this rule releases a total 24-hour volume
of 5 mcf or more of vapors, then a permittee of a well shall ensure that the vessel is
equipped with a vent line for conveying released gasses and vapors to an incinerator, flare,
or vapor recovery system. A flashback prevention system shall be installed on the line
between a vessel and the incinerator or flare. If a vapor recovery system is used to control
tank vapor emissions, then a flare or incinerator
shall be available for standby or emergency use. Installing a vapor recovery system does
not exempt a flare or incinerator from being in compliance with the requirements of R
324.1123.
(3) If a storage vessel described in subrule (1) of this rule releases a total daily volume of
5 mcf or more of vapors, then a permittee of a well shall install a fence around the vessel
equipped with a gate. A fence shall be located not less than 20 feet from the base of a
storage vessel. A permittee shall ensure that warning signs with the word "Danger" or
"Caution" followed by the words "Poison Gas" are installed on all sides of the fence. If the
supervisor or authorized representative of the supervisor finds that a threat to the public
safety exists due to emissions of sulfur-bearing gas or vapor, then fencing other than that
specified in R 324.102(p) may be required.
(4) If a storage vessel described in subrule (1) of this rule releases a total daily volume of
5 mcf or less of vapor, then it may be vented to the atmosphere if the vent is located not
less than 10 feet above the tank top and if the opening of the vent is within the diked area
or not less than 20 feet above the ground if the opening of the vent is outside the diked
area. The supervisor may prohibit venting of vapor to the atmosphere if a verified chronic
nuisance odor results from the sulfur-bearing compounds being vented.
(5) If the hydrogen sulfide concentration at the tank thief hatch is more than 500 ppm by
volume, then a permittee of a well shall ensure that a tank has a latched gate at the foot of
the catwalk stairs. A permittee of a well shall ensure that a sign reading "Self-contained
Breathing Apparatus is Recommended Beyond This Point if Hatches are to be Opened" is
posted on the gate.
(6) The supervisor may require the use of a tank gauging system that does not require the
opening of the tank hatches if a verified chronic nuisance odor results from tank gauging.
(7) A person or a permittee of a well shall not install a tank which is used for the storage
of hydrogen sulfide-bearing liquid hydrocarbons or brine from an H2S well if the separator
or treater immediately upstream of the tank has an operating pressure of more than 250
psig unless an independent
registered engineer certifies that the facility is designed and constructed such that any
release of liquids or gas to the tank shall not cause a release of hydrogen sulfide to the
atmosphere.