R 325.10604e
R 325.10604e Treatment techniques for acrylamide and epichlorohydrin.
Cite as Mich. Admin. Code R 325.10604e
Rule 604e. Each public water supply that uses acrylamide or epichlorohydrin in its
drinking water system shall provide annual written certification to the department, using
third party or manufacturer's certification, that the combination, or product, of dose and
monomer level is not more than 0.05% acrylamide dosed at 1 part per million, or
equivalent, and not more than 0.01% epichlorohydrin dosed at 20 parts per million, or
equivalent. This rule establishes treatment techniques for acrylamide and epichlorohydrin
in place of maximum contaminant levels.