R 325.10720
R 325.10720 Filtration and disinfection; filtration sampling requirements.
Cite as Mich. Admin. Code R 325.10720
Rule 720. (1) Subpart H supplies shall monitor under this rule to determine compliance
with R 325.10611a and R 325.10611b.
(2) All of the following provisions are turbidity monitoring requirements:
(a) Supplies shall collect samples and perform measurements for turbidity at locations
representative of filtered water at regular intervals at least once every 4 hours while the
treatment plant is in operation.
(b) A public water supply may substitute continuous turbidity monitoring for grab sample
monitoring if the continuous measurement is validated for accuracy on a regular basis using
a protocol approved by the department. Readings taken from a continuous recording
turbidimeter at regular intervals at least once every 4 hours may be used to determine
compliance with the treatment technique under R 325.10611b. The turbidimeter shall be
calibrated using the procedure specified by the manufacturer.
(c) Supplies using conventional or direct filtration shall conduct continuous monitoring
of turbidity for each individual filter and shall calibrate turbidimeters using the procedure
specified by the manufacturer. Supplies shall record the results of individual filter
monitoring every 15 minutes.
(d) If there is a failure in the continuous turbidity monitoring equipment described in
subdivision (c) of this subrule, then the supply shall conduct grab sampling every 4 hours
instead of continuous monitoring, but for not more than 5 working days after the failure of
the equipment for supplies serving 10,000 or more people or 14 days for supplies serving
fewer than 10,000 people before a violation is incurred.
(e) If the supply serves fewer than 10,000 people and consists of only 2 or fewer filters,
then the supply may conduct continuous monitoring of combined filter effluent turbidity
instead of individual filter effluent turbidity monitoring. Continuous monitoring shall meet
the same requirements in subdivisions (c) and (d) of this subrule.
(3) All of the following provisions are disinfectant residual monitoring requirements at
the entry points to the distribution system:
(a) Supplies serving more than 3,300 people shall monitor for residual disinfectant
concentration at an entry point to the distribution system on a continuous basis and record
the lowest value each day. If there is a failure in the continuous monitoring equipment, the
supply may take grab samples every 4 hours instead of continuous monitoring, but for no
more than 5 working days following the failure of the equipment.
(b) Supplies serving fewer than 3,301 people shall monitor for residual disinfectant
concentration at an entry point to the distribution system at a frequency set forth in table 1
of this rule, and, if more than 1 sample is required per day, supplies shall collect samples
at times evenly spaced throughout the operational day.
Table 1 Residual disinfectant concentration sampling frequencies
Supply size by population
Samples per day
500 or fewer people
1
501 to 1,000 people
2
1,001 to 2,500 people
3
2,501 to 3,300 people
4
(c) Under R 325.10611a, supplies shall maintain a residual disinfectant concentration
entering the distribution system of not less than 0.2 milligrams per liter. If the residual
disinfectant concentration drops below this level at any time, then the supply shall notify
the department as soon as possible, but not later than the end of the next business day. In
addition, the supply shall notify the department by the end of the next business day whether
or not the residual disinfectant concentration was restored to not less than 0.2 milligrams
per liter within 4 hours.
(4) The residual disinfectant concentration shall be measured, at least, at the same points
in the distribution system and at the same time as total coliforms are sampled, as specified
in R 325.10704 to R 325.10709 until March 31, 2016 and as specified in R 325.10704d to
R 325.10704h beginning April 1, 2016. The department may allow a public water supply
which uses both a surface water source or a ground water source under direct influence of
surface water, and a ground water source, to take disinfectant residual samples at points
other than the total coliform sampling points if the department determines that those points
are more representative of treated (disinfected) water quality within the distribution system.
Heterotrophic bacteria, measured as heterotrophic plate count (HPC) as adopted by
reference in R 325.10605, may be measured instead of residual disinfectant concentration.