R 325.10726
R 325.10726 Radionuclides; initial monitoring for gross alpha particle activity, radium-226, radium-228, and uranium.
Cite as Mich. Admin. Code R 325.10726
Rule 726. (1) A community water supply shall conduct initial monitoring for gross alpha
particle activity, radium-226, radium-228, and uranium to determine compliance with R
325.10603(2)(a), (b), and (d).
(2) An existing supply shall sample at every entry point to the distribution system that is
representative of all sources of water being used, known as "sampling point," under normal
operating conditions. The supply shall take each sample at the same sampling point unless
conditions make another sampling point more representative of each source.
(3) A new community water supply or a community water supply that uses a new source
of water shall begin to conduct initial monitoring for the new source within the first quarter
after initiating use of the source. A community water supply shall conduct more frequent
monitoring when ordered by the department if possible contamination or if changes in the
distribution system or treatment processes occur which may increase the concentration of
radioactivity in finished water.
(4) A supply shall conduct initial monitoring for gross alpha particle activity, radium-226,
radium-228, and uranium in the following manner:
(a) A supply shall collect 4 consecutive quarterly samples at all sampling points before
December 31, 2007. A supply that has results of samples collected from a sampling point
during the compliance period that began between June 1, 2000 and December 8, 2003, may
use those results to satisfy the initial monitoring requirements for that sampling point.
(b) For gross alpha particle activity, uranium, radium-226, and radium-228 monitoring,
the department may waive the final 2 quarters of initial monitoring for a sampling point if
the results of the samples from the previous 2 quarters are below the detection limit.
(c) If the average of the initial monitoring results for a sampling point is above the MCL,
then the supply shall collect and analyze quarterly samples at that sampling point until the
supply has results from 4 consecutive quarters that are at or below the MCL, unless the
supply enters into another schedule as part of a formal compliance agreement with the
department.