R 325.10730 Radionuclides; monitoring requirements for beta particle and photon radioactivity; applicability.
Cite as Mich. Admin. Code R 325.10730
Rule 730. (1) To determine compliance with the maximum contaminant levels in R
325.10603(2)(c) for beta particle and photon radioactivity, a community water supply, also
considered a "water supply" or "supply" in this rule, designated by the department as either
vulnerable or utilizing water contaminated by effluents from nuclear facilities, shall sample
for beta particle and photon radioactivity. The department's designation shall be based on
monitoring data, environmental surveillance data collected in the vicinity of nuclear
facilities, or source water assessments.
(2) Beginning within 1 quarter after being notified of the department's designation and
continuing until the department reviews and either reaffirms or removes the designation, a
supply shall collect samples at each entry point to the distribution system, known as
sampling point, under both of the following provisions:
(a) For a vulnerable supply, quarterly samples for beta emitters and annual samples for
tritium and strontium 90.
(b) For a supply utilizing waters contaminated by effluents from nuclear facilities,
quarterly samples for beta emitters and iodine 131 and annual samples for tritium and
strontium 90. A supply shall monitor and analyze the samples under all of the following
provisions:
(i) Quarterly monitoring for gross beta particle activity shall be based on the analysis of
monthly samples or the analysis of a composite of 3 monthly samples.
(ii) For iodine 131, a composite of 5 consecutive daily samples shall be analyzed once
each quarter. As ordered by the department, more frequent monitoring shall be conducted
when iodine 131 is identified in the finished water.
(iii) Annual monitoring for strontium 90 and tritium shall be conducted by means of the
analysis of a composite of 4 consecutive quarterly samples or analysis of 4 quarterly
samples.
(3) All of the following provisions apply for gross beta particle activity:
(a) A supply may analyze for naturally occurring potassium 40 beta particle activity from
the same or equivalent sample used for the gross beta particle activity analysis. A supply
may subtract the potassium 40 beta particle activity value from the total gross beta particle
activity value to determine if the screening level in subdivision (b) of this subrule is
exceeded. The potassium 40 beta particle activity shall be calculated by multiplying
elemental potassium concentrations (in mg/L) by a factor of 0.82.
(b) If the gross beta particle activity minus the naturally occurring potassium 40 beta
particle activity at a sampling point has a running annual average, computed quarterly, less
than or equal to a screening level of 50 pCi/L for a vulnerable supply or 15 pCi/L for a
supply utilizing waters contaminated by effluents from nuclear facilities, then the
department may reduce the frequency of monitoring at that sampling point to once every 3
years. During the reduced monitoring period, a supply shall collect the same type of
samples required in subrule (2)(a) of this rule for a vulnerable supply or subrule (2)(b) of
this rule for a supply utilizing water contaminated by effluents from nuclear facilities.
(c) If the gross beta particle activity minus the naturally occurring potassium 40 beta
particle activity exceeds the appropriate screening level in subdivision (b) of this subrule,
then an analysis of the sample shall be performed to identify the major radioactive
constituents present in the sample and the appropriate doses shall be calculated and
summed to determine compliance with R 325.10603(2)(c)(i), using the formula in R
325.10603(2)(c)(ii). Doses shall also be calculated and combined for measured levels of
tritium and strontium to determine compliance.
(4) For a supply in the vicinity of a nuclear facility, the community water supply may
utilize environmental surveillance data collected by the nuclear facility instead of
monitoring at the supply's entry point or points, where the department determines that the
data is applicable to a particular water supply. If there is a release from a nuclear facility,
then a supply which uses surveillance data shall begin monitoring at the community water
supply's entry point or points under subrule (2)(a) or (b) of this rule.
(5) A community water supply designated by the department to monitor for beta particle
and photon radioactivity shall not apply to the department for a waiver from the monitoring
frequencies specified in subrule (2)(a) or (b) of this rule.
(6) A supply shall monitor monthly at the sampling point or points that exceed the
maximum contaminant level in R 325.10603(2)(c) beginning the month after the
exceedance occurs. The supply shall continue monthly monitoring until the supply has
established, by the average of results from any 3 consecutive months, that the MCL is being
met. A supply that establishes that the MCL is being met shall return to quarterly
monitoring until it meets the requirements set forth in subrule (3)(b) of this rule.