R 325.10828 Casing vents; sampling tap; relief valves.
Cite as Mich. Admin. Code R 325.10828
Rule 828. (1) Casing vents shall be both of the following:
(a) Provided on all wells and constructed to prevent the entrance of contaminants into the
well.
(b) Extended to the outside atmosphere above the roof level if toxic or flammable gases
are present.
(2) Provisions shall be made for collection of raw water samples by installation of a proper
sampling tap in a convenient location as close to each well as possible. Provisions shall be
made for collection of finished water samples by installation of a proper sampling tap at
each entry point to the distribution system.
(3) Air vacuum relief valves, where used, shall be constructed to prevent entrance of
contaminants into the well.