R 325.11105 Capacity of distribution system; fire hydrants; inadequately sized watermains.
Cite as Mich. Admin. Code R 325.11105
Rule 1105. (1) Distribution systems shall have sufficient capacity to meet peak demands,
including fire flow demands where fire protection is provided, while continuously
maintaining a minimum of 35 psi throughout the distribution system under normal
operating conditions and 20 psi throughout the distribution system during emergencies
such as fire fighting.
(2) The department may prohibit installation of fire hydrants where watermain capacity,
system source capacity, storage capacity, or pressure is inadequate to sustain fire flow
demands in addition to normal user demands.
(3) Replacement of inadequately sized watermains with watermains of the same size is
prohibited.