R 325.11117 Storage tanks; disinfection and water analysis.
Cite as Mich. Admin. Code R 325.11117
Rule 1117. (1) Proper techniques shall be followed during construction to keep storage
tanks clean and dry.
(2) A finished water storage tank shall be disinfected before initial use and after any
internal maintenance or repair activity.
(3) Before placing a storage tank into service all of the following shall occur:
(a) Before collection of each bacteriologic sample, heavily chlorinated water shall be
flushed from the tank, drain piping, riser and all other appurtenances until the chlorine
measurements in the water leaving the tank is absent or no higher than that normally
maintained in the storage tank.
(b) Not fewer than 2 consecutive water samples for bacteriological analysis shall be
collected 24 hours apart unless an alternate interval is approved by the department.
(c) An analysis shall not indicate the presence of coliform. Analyses for other
contaminants may be required if the department has reason to believe that these
contaminants are present.