R 325.11403
R 325.11403 Cross-connections prohibited.
Cite as Mich. Admin. Code R 325.11403
Rule 1403. (1) A temporary or permanent unprotected cross connection between a public
water supply system and any source, piping, or system that may contain nonpotable water
or other substances is prohibited.
(2) Subrule (1) of this rule applies to all customer types, such as, industrial, commercial,
institutional, governmental, and single and multi-unit residential.
(3) Piping configurations creating the potential for water from a public distribution system
to flow through a private water main or customer site piping and back into the public system
are prohibited. Areas of private water main served by two or more service connections,
where flow through the private system can re-enter the public system shall have cross
connection control protection installed at each connection point to the public system.