R 325.1561
R 325.1561 Sewage disposal in modern campgrounds.
Cite as Mich. Admin. Code R 325.1561
Rule 11. (1) A campground owner shall connect his or her campground to a local
government sewer system, when available. A campground owner and person preparing
campground plans shall propose and provide a sewage treatment and disposal system that
is acceptable to the department if a local government system is not available.
(2) A person designing a campground sewage disposal system shall base the design
capacity of a facility described in subrule (1) of this rule on the following minimum
estimated daily liquid flows:
(a) For sites that have water and sewer outlets available to each site - 75 gallons per site.
(b) For sites served by service buildings - 75 gallons per site.
(c) For primitive sites operated in conjunction with a modern campground - 30 gallons
per day per primitive site.
(d) For sites for single sectional mobile homes and park model recreational units - 150
gallons per site.
(e) For other facilities operated in conjunction with a campground, a person designing a
campground sewage disposal system may use the "Michigan Criteria for Subsurface
Sewage Disposal," dated April 1994, as a reference in estimating daily design flow. This
publication can be obtained from the Michigan Department of Environmental Quality,
Drinking Water and Radiological Protection Division, Environmental Health Section, P.O.
Box 30630, Lansing, Michigan 48909-8130.
(3) A campground owner shall ensure that a sewer service riser which is located at a site
on a sewer system is trapped. A campground owner shall ensure that a service riser which
is designed for winter use is trapped below the frost line. A campground owner shall ensure
that the trap and riser is constructed of cast iron or rigid plastic pipe as approved by the
plumbing division of the Michigan department of consumer and industry services. A
campground owner shall ensure that the top of the riser extends not less than 2 inches above
the surrounding ground surface. A campground owner shall ensure that a riser is capped
when not in use. A campground owner shall ensure that the sewer service riser is not
located closer than 5 feet from a water riser.
(4) A campground owner shall provide a sewer service riser to a campsite occupied by a
single sectional mobile home.
(5) A campground owner shall ensure that a gravity sanitary sewer has sufficient capacity
to accommodate the maximum hourly flow from the portion of the campground being
served and is not less than 4 inches in diameter.
(6) A campground owner shall ensure that a sanitary sewer has a minimum depth of bury
of 2 feet. If the sanitary sewer is designed for winter use, then the campground owner shall
ensure that the sewer system has a minimum depth of bury of 3.5 feet or more than 3.5 feet
in areas where the frost line typically extends below 3.5 feet.
(7) A campground owner shall ensure that a sanitary sewer is installed with sufficient
slope to maintain a velocity of 2 feet per second at design flow.
(8) A campground owner shall ensure that all sanitary sewers which are less than 10
inches in diameter have cleanouts located at the end of each sewer line; at all changes in
grade, size, and direction of more than 45 degrees; and at distances of not more than 100
feet along sewers.
(9) A campground owner shall ensure that all sewers which are 10 inches in diameter or
larger have manholes located at all changes in grade, size, and direction and at distances of
not more than 400 feet along sewers. A campground owner shall ensure that a flow channel
through a manhole conforms to the slope and shape of the sanitary sewers.
(10) A person designing the campground sewage system shall specify leakage tests for
the proposed construction of sanitary sewers.
(11) A campground owner shall ensure that a sanitary sewer or individual sewer service
line is not laid within 10 feet horizontally of a waterline.
(12) If a sanitary sewer line crosses a waterline, then a campground owner shall ensure
that there is a minimum of 12 inches of clear vertical isolation between the sewer line and
the waterline. If it is not feasible to have a minimum of 12 inches of vertical isolation, then
a campground owner shall ensure that the sanitary sewer line is encased in concrete for 5
feet on each side of the crossing. A campground owner shall ensure that 1 full length of
waterline is centered over the sewer crossing.