R 325.1627
R 325.1627 Construction of wells; steel casing and types of joints.
Cite as Mich. Admin. Code R 325.1627
Rule 127. (1) Steel pipe that is used as permanent well casing shall be watertight
throughout its length and shall have threaded or welded joints.
(2) Couplings that are used on threaded steel casing shall be recessed or reamed and
drifted couplings that are manufactured in compliance with the standards of ASTM
specification A 589-89a or API specification 5L-90. The specifications are adopted by
reference in R 325.1610. Couplings shall have a design, taper, and type of thread that is
consistent with the thread of the pipe and threads shall not be exposed on the pipe.
(3) Welded joints shall be in compliance with the specifications of table 2 and provide a
structurally sound and watertight joint. Pipe ends shall be free of oil, grease, heavy rust,
paint, or other foreign
materials, except for tightly adherent mill scale. The weld bead shall be chipped and
brushed to remove slag and other extraneous materials between passes.
Table 2
Minimum Number of Passes
for Welding Steel Casing
Pipe Diameter Minimum Number
(inches)
passes
4
2
5
2
6
3
8
3
10 or larger
4