R 325.1655
R 325.1655 Pump installation; water service lines.
Cite as Mich. Admin. Code R 325.1655
Rule 155. (1) The buried portion of a water service line between the well casing and the
pressure tank in any installation shall be under positive pressure at all times. If a check
valve is installed in the water line between the well casing and the pressure tank, the water
line between the well casing and the check valve shall be in compliance with the
requirements for a suction line pursuant to the provisions of R 325.1654.
(2) Plastic water service line material shall have a minimum rated working pressure of
160 pounds per square inch, shall be in compliance with ASTM specification D 2239-89,
D 2737-89, D 2662-89, D 2666-89, D 1785-91, or D 2241-89, which specifications are
adopted by reference in R 325.1610.