R 325.1661
R 325.1661 Disinfection of well and pumping equipment.
Cite as Mich. Admin. Code R 325.1661
Rule 161. (1) After thoroughly pumping to waste pursuant to the provisions of R
325.1639(5), a well and pumping equipment shall be disinfected with chlorine that is
applied to obtain a chlorine concentration and minimum contact period specified in table 5
in all parts of the water supply system before pumping the well to waste and flushing out
the chlorine solution. A well drilling contractor or pump installer shall be responsible for
chlorinating that portion of the water supply system on which work has been performed.
Table 5
Minimum Chlorine Concentration and Contact Time
Amount of Chlorine Added to
100 Gallons of Water
Pounds of
Chlorine Gallons of 5.25%
Dry Calcium Minimum
Concentration Sodium Hypochlorite Hypochlorite
Contact
(Parts per Million) (Liquid Bleach)
(Granular)
Time
100 ppm 1/4 gal 0.14 lbs 10 hr
250 ppm 1/2 gal 0.35 lbs 4 hr
500 ppm 1 gal 0.70 lbs 2 hr
1000 ppm 2 gal 1.40 lbs 1 hr
(2) Before placing a new, repaired, or reconditioned water supply system into service, and
after all traces of chlorine have been flushed out, 1 or more water samples shall be collected
from the sampling faucet. Organisms of the coliform group shall not be present in the
sample or samples.
(3) The water supply owner shall be responsible for collecting the water sample or shall
arrange for the owner's designated representative to collect the sample. The well drilling
contractor or pump installer shall notify the water supply owner of the owner's
responsibility for collecting the water sample.
(4) A well driller or pump installer is not required to redisinfect a well or pump as a result
of water samples that are collected from a location other than the sampling faucet required
pursuant to the provisions of R 325.1658.