R 325.17701
R 325.17701 Control of solvent and solvent vapors; exhaust ventilation generally.
Cite as Mich. Admin. Code R 325.17701
Rule 701. (1) Dry cleaning systems in type I, II, III, and IV dry cleaning establishments
shall be installed and maintained to prevent the unnecessary escape of solvents or solvent
vapors into the dry cleaning machine room and public area atmospheres and so that the
vapor concentration shall not exceed the allowable concentration in these areas for those
compounds as specified in R 325.51101 et seq.
(2) General mechanical exhaust ventilation shall be provided in a dry cleaning machine
room to effectively control the buildup of dry cleaning solvent vapors. The exhaust
ventilation system shall be designed and installed to have a minimum capacity of 1
complete change of air in the dry cleaning machine room each 5 minutes in order to control
emergency spills or leaks.